| Title: | Optimal control strategy of central air-conditioning systems of buildings at morning start period for enhanced energy efficiency and peak demand limiting | Authors: | Tang, R Wang, S Shan, K Cheung, H |
Issue Date: | 15-May-2018 | Source: | Energy, 15 May 2018, v. 151, p. 771-781 | Abstract: | Air-conditioning systems in commercial buildings are usually switched on before office hour to precool buildings to create an acceptable working environment at the beginning of the office hour in cooling seasons. However, due to high cooling demand during morning start period particularly in hot seasons, often much higher than the capacity of cooling supply, the feedback control strategies in air-conditioning systems often fail to control this cooling process properly. The imbalanced cooling distribution and large difference of cooling-down speeds among different spaces result in the need of significantly extended precooling duration as well as over-speeding of water pumps and fans that lead to serious energy waste and high peak demand. An optimal control strategy is therefore developed to determine the number and schedule of operating chillers and particularly to achieve an optimal cooling distribution among individual spaces. Case studies are conducted and results show that the proposed control strategy could shorten the precooling time about half an hour because of similar cooling-down speeds among individual zones. The energy consumption of the air-conditioning system during morning start period is also reduced over 50%. In addition, the peak demand is reduced significantly contributed by the improved controls of secondary pumps and fans. | Keywords: | Air-conditioning Building energy efficiency Indoor environment control Peak load limiting Precooling control |
Publisher: | Pergamon Press | Journal: | Energy | ISSN: | 0360-5442 | EISSN: | 1873-6785 | DOI: | 10.1016/j.energy.2018.03.032 | Rights: | © 2018 Elsevier Ltd. All rights reserved. © 2018. This manuscript version is made available under the CC-BY-NC-ND 4.0 license https://creativecommons.org/licenses/by-nc-nd/4.0/ The following publication Tang, R., Wang, S., Shan, K., & Cheung, H. (2018). Optimal control strategy of central air-conditioning systems of buildings at morning start period for enhanced energy efficiency and peak demand limiting. Energy, 151, 771-781 is available at https://doi.org/10.1016/j.energy.2018.03.032. |
| Appears in Collections: | Journal/Magazine Article |
Files in This Item:
| File | Description | Size | Format | |
|---|---|---|---|---|
| Tang_Optimal_Control_Strategy.pdf | Pre-Published version | 2.8 MB | Adobe PDF | View/Open |
Page views
131
Last Week
1
1
Last month
Citations as of Nov 9, 2025
Downloads
678
Citations as of Nov 9, 2025
SCOPUSTM
Citations
66
Citations as of Dec 19, 2025
WEB OF SCIENCETM
Citations
47
Citations as of Dec 18, 2025
Google ScholarTM
Check
Altmetric
Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.