Please use this identifier to cite or link to this item: http://hdl.handle.net/10397/9989
Title: A case study on the application of air- and water-cooled oil-free chillers to hospitals in Hong Kong
Authors: Yik, FWH
Lai, JHK 
Fong, NK 
Leung, PHM 
Yuen, PL
Issue Date: 2012
Publisher: SAGE Publications
Source: Building services engineering research and technology, 2012, v. 33, no. 3, p. 263-279 How to cite?
Journal: Building services engineering research and technology 
Abstract: A comparison study on using air-cooled and water-cooled conventional and oil-free chillers in hospitals in Hong Kong is reported. The study commenced with a comprehensive literature review to reaffirm the effectiveness of recommended precaution measures for containing the risk of Legionnaires' disease (LD) associated with using cooling towers. Numerical performance models for oil-free chillers established for use in the study are presented. Based on recorded cooling demands of two existing hospitals, the life-cycle energy consumption and cost of system options involving different combinations of heat rejection method and chiller type were evaluated, compared and discussed. The results show that water-cooled air-conditioning systems with conventional chillers and cooling towers are still more energy efficient than air-cooled systems with oil-free chillers. Water-cooled oil-free chillers may become an economically viable choice when their price is lowered in future. Pilot installation is recommendable, as it would allow the reliability and maintainability of the new oil-free chillers to be ascertained.Practical applications: Findings of the literature review reaffirmed the effectiveness of measures recommended in contemporary guidelines for LD prevention, which would ease the mind of owners, designers and operation and maintenance personnel in regard of using cooling towers in hospitals. The numerical models for oil-free chillers presented in the paper are useful for evaluation of the energy consumption of this new type of chiller and for comparison with other types of chillers. The study approach described in the paper, including the energy consumption prediction and life-cycle cost evaluation methods, provides a useful framework for similar studies.
URI: http://hdl.handle.net/10397/9989
ISSN: 0143-6244
EISSN: 1477-0849
DOI: 10.1177/0143624411408034
Appears in Collections:Journal/Magazine Article

Access
View full-text via PolyU eLinks SFX Query
Show full item record

SCOPUSTM   
Citations

1
Last Week
0
Last month
0
Citations as of Aug 14, 2017

WEB OF SCIENCETM
Citations

1
Last Week
0
Last month
0
Citations as of Aug 13, 2017

Page view(s)

90
Last Week
1
Last month
Checked on Aug 13, 2017

Google ScholarTM

Check

Altmetric



Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.