Please use this identifier to cite or link to this item: http://hdl.handle.net/10397/60899
PIRA download icon_1.1View/Download Full Text
Title: Real time control of chilled water supervisory controller in central air conditioning systems
Other Title: 集中空调冷水侧局部系统上位机控制器的实时控制分析
Authors: Meng, H
Long, WD
Wang, SW 
Issue Date: 2005
Source: 暖通空調 (HV & A), 2005, v. 35, no. 11, p. 96-100, 136
Abstract: 针对集中空调冷水侧基本自动控制系统,设计了两个上位机控制器,分别仅对供回水压差和同时对压差与冷水供水温度进行实时优化;通过仿真实验分析了控制器对系统控制稳定性和系统能耗的影响。结果表明,综合考虑制冷机和二次泵系统的上位机控制器具有较好的可实施性,能在保证系统运行稳定的前提下减少冷水侧能耗。 
From the viewpoint of basic automatic control system, designs two chilled water supervisory controllers and applies them to digital simulators to real time control of the supply/return pressure difference and of both the difference and the supply chilled water temperature. Analyses the influences of the supervisory controller on control stability and energy consumption of the system by simulation experiment. The simulation results show that the controller making trade off between chillers and chilled water pumps is practicable in saving the total energy of chilled water system while still keeping the control stability.
Keywords: Central air conditioning
Chilled water system
Supervisory controller
Real time control
Publisher: 中國學術期刊(光盤版)電子雜誌社
Journal: 暖通空調 (HV & A) 
ISSN: 1002-8501
Rights: © 2005 中国学术期刊电子杂志出版社。本内容的使用仅限于教育、科研之目的。
© 2005 China Academic Journal Electronic Publishing House. It is to be used strictly for educational and research use.
Appears in Collections:Journal/Magazine Article

Files in This Item:
File Description SizeFormat 
r29252.pdf672.59 kBAdobe PDFView/Open
Open Access Information
Status open access
File Version Version of Record
Access
View full-text via PolyU eLinks SFX Query
Show full item record

Page views

197
Last Week
2
Last month
Citations as of Apr 14, 2024

Downloads

70
Citations as of Apr 14, 2024

Google ScholarTM

Check


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.