Please use this identifier to cite or link to this item: http://hdl.handle.net/10397/98710
PIRA download icon_1.1View/Download Full Text
Title: Connection between damping torque analysis and energy flow analysis in damping performance evaluation for electromechanical oscillations in power systems
Authors: Hu, Y 
Bu, S 
Zhang, X
Chung, CY 
Cai, H
Issue Date: Jan-2022
Source: Journal of modern power systems and clean energy, Jan. 2022, v. 10, no. 1, p. 19-28
Abstract: The damping performance evaluation for electro-mechanical oscillations in power systems is crucial for the stable operation of modern power systems. In this paper, the connection between two commonly-used damping performance evaluation methods, i.e., the damping torque analysis (DTA) and energy flow analysis (EFA), are systematically examined and revealed for the better understanding of the oscillatory damping mechanism. First, a concept of the aggregated damping torque coefficient is proposed and derived based on DTA of multi-machine power systems, which can characterize the integration effect of the damping contribution from the whole power system. Then, the pre-processing of measurements at the terminal of a local generator is conducted for EFA, and a concept of the frequency-decomposed energy attenuation coefficient is defined to screen the damping contribution with respect to the interested frequency. On this basis, the frequency spectrum analysis of the energy attenuation coefficient is employed to rigorously prove that the results of DTA and EFA are essentially equivalent, which is valid for arbitrary types of synchronous generator models in multi-machine power systems. Additionally, the consistency between the aggregated damping torque coefficient and frequency-decomposed energy attenuation coefficient is further verified by the numerical calculation in case studies. The relationship between the proposed coefficients and the eigenvalue (or damping ratio) is finally revealed, which consolidates the application of the proposed concepts in the damping performance evaluation.
Keywords: Damping performance
Damping torque analysis (DTA)
Electromechanical oscillation
Energy flow analysis (EFA)
Frequency spectrum
Publisher: Institute of Electrical and Electronics Engineers
Journal: Journal of modern power systems and clean energy 
ISSN: 2196-5625
EISSN: 2196-5420
DOI: 10.35833/MPCE.2020.000413
Rights: This article is distributed under the terms of the Creative Commons Attribution 4.0 International License (http://creativecommons.org/licenses/by/4.0/).
The following publication Hu, Y., Bu, S., Zhang, X., Chung, C. Y., & Cai, H. (2021). Connection between damping torque analysis and energy flow analysis in damping performance evaluation for electromechanical oscillations in power systems. Journal of Modern Power Systems and Clean Energy, 10(1), 19-28 is available at https://doi.org/10.35833/MPCE.2020.000413.
Appears in Collections:Journal/Magazine Article

Files in This Item:
File Description SizeFormat 
Hu_Connection_Damping_Torque.pdf891.97 kBAdobe PDFView/Open
Open Access Information
Status open access
File Version Version of Record
Access
View full-text via PolyU eLinks SFX Query
Show full item record

Page views

125
Citations as of Apr 14, 2025

Downloads

41
Citations as of Apr 14, 2025

SCOPUSTM   
Citations

14
Citations as of Sep 12, 2025

WEB OF SCIENCETM
Citations

11
Citations as of Dec 18, 2025

Google ScholarTM

Check

Altmetric


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.