Title: Model development of heat/mass transfer for internally cooled dehumidifier concerning liquid film shrinkage shape and contact angles
Authors: Dong, C 
Lu, L 
Qi, R 
Issue Date: Mar-2017
Source: Building and environment, Mar. 2017, v. 114, p. 11-22
Abstract: Moisture affects building materials, the thermal comfort of building occupants and the work performed by them. The plate liquid desiccant air-conditioning system (LDACS) is a promising dehumidification alternative to traditional air-conditioning system for lower energy consumption and less pollution. The shrinkage of the falling film on working plates critically influences the dehumidification performance by affecting the wetting area and film thickness. This paper developed a new model of plate dehumidifier concerning the shrinkage shape and the variable film thickness of falling film. The new model was validated by experiments and compared with existing models. The results indicated that the effect of contact angles on dehumidification performance can be accurately predicted. The moisture removal rates increased rapidly from 2.0 g/kg to 2.56 g/kg as the contact angles decreased from 85° to 5°, while the wetting area increased from 0.145 m2 to 0.176 m2. The distribution of the humidity ratio of process air along flow direction with different contact angles was also simulated. Besides, the average film thickness decreased from 0.952 mm to 0.889 mm as the contact angles decreased from 85° to 5°. The annual electricity consumption of plate LDACS with different contact angles for a typical building in Hong Kong was estimated and analysed by using the newly developed model. The new model can achieve a better predictive accuracy by considering the exact shrinkage shape of falling film and the findings can provide a new insights improving the performance of plate dehumidifiers and other industrial applications, such as vertical condensers, evaporators and absorption towers.
Keywords: Contact angle
Dehumidification performance
Liquid desiccant air-conditioning system
Shrinkage shape
Wetting area
Publisher: Pergamon Press
Journal: Building and environment 
ISSN: 0360-1323
EISSN: 1873-684X
DOI: 10.1016/j.buildenv.2016.12.001
Rights: © 2016 Elsevier Ltd. All rights reserved.
© 2016. This manuscript version is made available under the CC-BY-NC-ND 4.0 license https://creativecommons.org/licenses/by-nc-nd/4.0/
The following publication Dong, C., Lu, L., & Qi, R. (2017). Model development of heat/mass transfer for internally cooled dehumidifier concerning liquid film shrinkage shape and contact angles. Building and Environment, 114, 11-22 is available at https://doi.org/10.1016/j.buildenv.2016.12.001.
Appears in Collections:Journal/Magazine Article

Files in This Item:
File Description SizeFormat 
Model_Development_Heat.pdfPre-Published version1.38 MBAdobe PDFView/Open
Open Access Information
Status open access
File Version Final Accepted Manuscript
Access
View full-text via PolyU eLinks SFX Query
Show full item record

Page views

141
Last Week
3
Last month
Citations as of Nov 9, 2025

Downloads

125
Citations as of Nov 9, 2025

SCOPUSTM   
Citations

40
Citations as of Dec 19, 2025

WEB OF SCIENCETM
Citations

39
Citations as of Dec 18, 2025

Google ScholarTM

Check

Altmetric


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.