Title: Waterfront hotels’ chillers : energy benchmarking and ESG reporting
Authors: Lau, C 
Tang, ILF
Chan, W
Issue Date: Jun-2021
Source: Sustainability, June 2021, v. 13, no. 11, 6242
Abstract: Chillers consumes the largest amount power in subtropical hotels. To monitor chillers’ power usage is of critical importance in energy control. This study attempted to establish the benchmark of electricity usage of hotel chillers and elucidate how the benchmarking results can be integrated with the various types reports for monitoring purposes. A survey of 20 waterfront hotels in the city of Greater Bay Area was conducted and 13 complete samples were used in the analysis. Multiple regression with selected 12 parameters—outdoor temperature, solar radiation, wind speed, cooling degree days, room occupancy, number of employees, service types, and unequally sized chillers were employed. The investigation found that the mean electricity usage of a chiller is 118 kWh/m2 on an annual basis for a deluxe waterfront hotel. The analysis excluded air-conditioned floor area, an exploratory variable, as the valid factor in the chiller’s electricity usage. While the overall R2 of the modeling equation for the whole year was limited to 0.76, the explanatory power of equations for humid spring and deep summer reached 80%. Hoteliers may harness this exercise as a reference to monitor and report the performance of key energy production facility per the Environment, Social, and Governance (ESG) guide.
Keywords: ESG reports
Greater Bay Area
Water-cooled chillers
Waterfront hotel
Publisher: Molecular Diversity Preservation International (MDPI)
Journal: Sustainability 
EISSN: 2071-1050
DOI: 10.3390/su13116242
Rights: © 2021 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https:// creativecommons.org/licenses/by/ 4.0/).
The following publication : Lau, C.; Tang, I.L.F.; Chan, W. Waterfront Hotels’ Chillers: Energy Benchmarking and ESG Reporting. Sustainability 2021, 13, 6242 is available at https://doi.org/10.3390/su13116242
Appears in Collections:Journal/Magazine Article

Files in This Item:
File Description SizeFormat 
sustainability-13-06242.pdf708.76 kBAdobe PDFView/Open
Open Access Information
Status open access
File Version Version of Record
Access
View full-text via PolyU eLinks SFX Query
Show full item record

Page views

73
Last Week
0
Last month
Citations as of Apr 21, 2024

Downloads

32
Citations as of Apr 21, 2024

SCOPUSTM   
Citations

3
Citations as of Apr 19, 2024

WEB OF SCIENCETM
Citations

4
Citations as of Apr 18, 2024

Google ScholarTM

Check

Altmetric


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.