Title: Experimental scale model study on explosion of clean refrigerant leaked in an underground plant room
Authors: Gao, ZM
Gao, Y
Chow, WK 
Wan, Y 
Chow, CL
Issue Date: Aug-2018
Source: Tunnelling and underground space technology, Aug. 2018, v. 78, p. 35-46
Abstract: Several clean refrigerants widely used in new air-conditioning systems are composed of flammable propane. Leakage of the flammable refrigerant from the air-conditioning systems housed in a basement plant room would pose fire and explosion hazards. However, very few studies have been carried out to study explosion hazards of leaked clean refrigerant in underground spaces. In this paper, a model chamber with two common mechanical ventilation designs in basement plant room was used to study experimentally the hazards. Clean flammable refrigerant was discharged to the model chamber to a concentration level less than the lower flammability limit. Four sets of tests with different ventilation conditions were carried. Concentrations of the leaked refrigerant at. different positions in the chamber under different ventilation conditions were measured. Explosion of leaked gas was triggered by ignition. After ignition the transient gas temperature and pressure inside the model were recorded. Results indicate that mixing of leaked flammable refrigerant, and hence the concentrations of the leaked gas, depends on the mechanical ventilation design in the chamber. Improper ventilation provision would result in high refrigerant-to-air mixing ratio at some positions, even though the designed leaked refrigerant concentration is less than the lower flammable limit calculated from a well-mixing model. The results of the present study would contribute to better understanding of explosion hazards due to leakage of flammable refrigerant in green air-conditioning and refrigeration system in basement plant room or similar enclosures.
Keywords: Explosion
Clean refrigerants
Air-conditioning and refrigeration system
Ventilation
Publisher: Pergamon Press
Journal: Tunnelling and underground space technology 
ISSN: 0886-7798
DOI: 10.1016/j.tust.2018.04.010
Rights: © 2018 Elsevier Ltd. All rights reserved.
© 2018. This manuscript version is made available under the CC-BY-NC-ND 4.0 license https://creativecommons.org/licenses/by-nc-nd/4.0/
The following publication Gao, Z. M., Gao, Y., Chow, W. K., Wan, Y., & Chow, C. L. (2018). Experimental scale model study on explosion of clean refrigerant leaked in an underground plant room. Tunnelling and underground space technology, 78, 35-46 is available at https://doi.org/10.1016/j.tust.2018.04.010.
Appears in Collections:Journal/Magazine Article

Files in This Item:
File Description SizeFormat 
Experimental_Scale_Model.pdfPre-Published version2.07 MBAdobe PDFView/Open
Open Access Information
Status open access
File Version Final Accepted Manuscript
Access
View full-text via PolyU eLinks SFX Query
Show full item record

Page views

96
Last Week
0
Last month
Citations as of Mar 24, 2024

Downloads

40
Citations as of Mar 24, 2024

SCOPUSTM   
Citations

9
Citations as of Mar 29, 2024

WEB OF SCIENCETM
Citations

8
Last Week
0
Last month
Citations as of Mar 28, 2024

Google ScholarTM

Check

Altmetric


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.