Please use this identifier to cite or link to this item: http://hdl.handle.net/10397/115399
PIRA download icon_1.1View/Download Full Text
Title: Distributed temperature sensor model for linear heat detection in tunnel fires
Authors: Bielawski, J 
Luan, D 
Zhang, X 
Xie, W 
Huang, X 
Węgrzyński, W
Issue Date: Jan-2026
Source: Tunnelling and underground space technology, Jan. 2026, v. 167, 107092
Abstract: This study proposes a method for implementing distributed temperature sensing systems in tunnel fire simulations. A review of the investigations was conducted, and previous research on linear heat detection was examined. The characteristics and operational parameters of a complete DTS-based LHD system in a road tunnel are presented. A heat transfer model of the DTS sensor cable for CFD modelling was developed based on experiments in the standardised EN 54–5 wind tunnel for testing heat sensors. Based on the data analysis, substitute physical properties of the sensor cable were selected for the heat transfer model to allow implementation of the DTS model in CFD. Concurrently, an RTI value of 90 (m/s)1/2 was approximated to compare the model with the response-time model commonly used in fire engineering analyses. To validate the model, two full-scale fire tests were carried out in a road tunnel in Świnoujście, Poland, and CFD numerical simulations were performed with the proposed DTS model. The relative error of detection time prediction was within 3% for the case with low velocity, and successfully predicted no detection in the case with high velocity (>1 m/s). The developed model allows to tracking temperature changes of the DTS sensor cable with satisfactory precision and can be applied in various tunnel fire analyses.
Keywords: CFD fire model
DTS
Fiber optical sensor
Fire detection
Linear heat detection
Tunnel fire
Publisher: Elsevier Ltd
Journal: Tunnelling and underground space technology 
ISSN: 0886-7798
EISSN: 1878-4364
DOI: 10.1016/j.tust.2025.107092
Rights: © 2025 The Authors. Published by Elsevier Ltd. This is an open access article under the CC BY license (http://creativecommons.org/licenses/by/4.0/).
The following publication Bielawski, J., Luan, D., Zhang, X., Xie, W., Huang, X., & Węgrzyński, W. (2026). Distributed temperature sensor model for linear heat detectionintunnelfires. Tunnelling and Underground Space Technology, 167, 107092 is available at https://doi.org/10.1016/j.tust.2025.107092.
Appears in Collections:Journal/Magazine Article

Files in This Item:
File Description SizeFormat 
1-s2.0-S0886779825007308-main.pdf13.46 MBAdobe PDFView/Open
Open Access Information
Status open access
File Version Version of Record
Access
View full-text via PolyU eLinks SFX Query
Show full item record

Google ScholarTM

Check

Altmetric


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.