| Title: | Generic load regulation strategy for enhancing energy efficiency of chiller plants | Authors: | Wan, H Gong, Y Wang, S Sun, Y Xu, T Huang, G |
Issue Date: | Aug-2024 | Source: | Building simulation, Aug. 2024, v. 17, no. 8, p. 1273-1287 | Abstract: | In many chiller plants, high coefficient of performance (COP) is only achieved at a few favorable part load ratios (PLRs), while the COP is low at many other non-favorable PLRs. To address this issue, this study proposes a generic load regulation strategy that aims to maintain chiller plants operating at high COP, particularly under non-favorable PLRs. This is achieved by incorporating thermal energy storage (TES) units and timely optimizing the charging and discharging power of the integrated TES units. The optimal charging and discharging power is determined by solving a dynamic optimization problem, taking into account the performance constraints of the TES units and the chiller plants. To provide an overview of the energy-saving potential of the proposed strategy, a comprehensive analysis was conducted, considering factors such as building load profiles, COP/PLR curves of chillers, and attributes of the TES units. The analysis revealed that the proposed load regulation strategy has the potential to achieve energy savings ranging from 5.7% to 10.8% for chiller plants with poor COPs under unfavorable PLRs, particularly in buildings with significant load variations. | Keywords: | Building energy efficiency Chiller plants Load regulation Thermal energy storage |
Publisher: | Tsinghua University Press | Journal: | Building simulation | ISSN: | 1996-3599 | EISSN: | 1996-8744 | DOI: | 10.1007/s12273-024-1138-1 | Rights: | © The Author(s) 2024 This article is licensed under a Creative Commons Attribution 4.0 International License, which permits use, sharing, adaptation, distribution and reproduction in any medium or format, as long as you give appropriate credit to the original author(s) and the source, provide a link to the Creative Commons license, and indicate if changes were made. The images or other third party material in this article are included in the article’s Creative Commons license, unless indicated otherwise in a credit line to the material. If material is not included in the article’s Creative Commons license and your intended use is not permitted by statutory regulation or exceeds the permitted use, you will need to obtain permission directly from the copyright holder. To view a copy of this license, visit http://creativecommons.org/licenses/by/4.0/ The following publication Wan, H., Gong, Y., Wang, S. et al. Generic load regulation strategy for enhancing energy efficiency of chiller plants. Build. Simul. 17, 1273–1287 (2024) is available at https://doi.org/10.1007/s12273-024-1138-1. |
| Appears in Collections: | Journal/Magazine Article |
Files in This Item:
| File | Description | Size | Format | |
|---|---|---|---|---|
| s12273-024-1138-1.pdf | 3.47 MB | Adobe PDF | View/Open |
Page views
27
Citations as of Apr 14, 2025
Downloads
6
Citations as of Apr 14, 2025
SCOPUSTM
Citations
5
Citations as of Sep 12, 2025
Google ScholarTM
Check
Altmetric
Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.