| Title: | Preparing for the next pandemic : minimizing airborne transmission in general inpatient wards through management practices | Authors: | Tsang, TW Wong, LT Mui, KW Satheesan, MK Yuen, JWM |
Issue Date: | 1-Sep-2023 | Source: | Energy and buildings, 1 Sept 2023, v. 294, 113214 | Abstract: | Existing infection control studies in hospitals focused on rooms with special ventilation requirements. Study on proper management practices and ventilation strategies in general inpatient wards are critical but currently lacking. To identify the simple operational practices that can limit airborne transmission within a general inpatient ward with the patient cubicle, nursing station and corridor, this study investigates the effects of infected patient locations, air change rates (ACH) and door opening angles on bioaerosol dispersion using a novel tracer gas sensor network. Experimental results show that the supply inlet and infected patient locations significantly affects the distribution and dispersion of the tracer gas within the ward. Using a higher ventilation rate to achieve a lower average airborne pathogen concentration can cause more mixing of air and a wider dispersion of airborne pathogens. Localization of bioaerosols near the source through ventilation controls, a low ACH and proper patient location near the exhaust can minimize the air turbulence and the spread and reduce the infection risks of the susceptibles. Using physical partitions or objects as shields against airborne contaminants can unpredictably influence the airflow patterns, airflow evaluations should hence be done on a case-by-case basis. The methodology established in this study puts forward an economical and fast way for evaluating airborne infection risk, and the experimental results can be useful references for building engineers and hospital facility managers to formulate proper strategies for risk assessment and infection control. | Keywords: | Airborne transmission Healthcare-associated infections Infection risk Tracer gas experiment Wireless sensor network |
Publisher: | Elsevier BV | Journal: | Energy and buildings | ISSN: | 0378-7788 | EISSN: | 1872-6178 | DOI: | 10.1016/j.enbuild.2023.113214 | Rights: | © 2023 Elsevier B.V. All rights reserved. © 2023. This manuscript version is made available under the CC-BY-NC-ND 4.0 license https://creativecommons.org/licenses/by-nc-nd/4.0/ The following publication Tsang, T.-W., Wong, L.-T., Mui, K.-W., Satheesan, M. K., & Yuen, J. W.-M. (2023). Preparing for the next pandemic: Minimizing airborne transmission in general inpatient wards through management practices. Energy and Buildings, 294, 113214 is available at https://doi.org/10.1016/j.enbuild.2023.113214. |
| Appears in Collections: | Journal/Magazine Article |
Files in This Item:
| File | Description | Size | Format | |
|---|---|---|---|---|
| Tsang_Preparing_Next_Pandemic.pdf | Pre-Published version | 1.77 MB | Adobe PDF | View/Open |
Page views
58
Citations as of Apr 14, 2025
SCOPUSTM
Citations
7
Citations as of Dec 5, 2025
WEB OF SCIENCETM
Citations
2
Citations as of Apr 3, 2025
Google ScholarTM
Check
Altmetric
Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.