| Title: | Response surface modeling and optimization scheme of an internally cooled liquid desiccant air conditioning system | Authors: | Zhang, Y Zhang, H Yang, H Chen, Y Leung, CW |
Issue Date: | 1-Oct-2023 | Source: | Journal of building engineering, 1 Oct. 2023, v. 76, 107371 | Abstract: | Applying an internally cooled liquid desiccant air conditioning system (LDAC) is a promising energy-saving and emission-reduction scheme for hot and humid areas. This research investigates the application of an internally cooled LDAC for performance enhancement in hot and humid areas like Hong Kong. The combined system integrates liquid desiccant dehumidification (LDD) and regenerative indirect evaporative cooling (RIEC) without a power-intensive compressor. The internally cooled LDD removes latent heat from the hot and humid air before the RIEC cools it. To ensure efficient energy utilization, the LDD captures the exhaust air to assist in the dehumidification and initial cooling of the fresh air, which alleviates the efficiency deterioration of the desiccant. An all-fresh air system is used for better indoor air quality. To optimize the performance of a system with many influencing parameters, the response surface method (RSM) and multi-objective optimization are used to optimize and assess the potential and performance of the system. The system cooling capacity (C), latent heat removal rate (Qd), and dehumidification efficiency (ηd) are used as the optimization objectives. The response surface model and desirability function approach optimize six critical parameters, achieving a 7.6% improvement in dehumidification performance with low airspeed (1.5 m/s) and high desiccant concentration (40%) during high-humidity months. Increasing the extraction ratio of the RIEC by 20% in warmer months enhances the peak cooling capacity by 23.6%. This research contributes to implementing internally cooled LDAC systems and provides insights into optimizing monthly operation patterns in hot and humid regions. | Keywords: | Indirect evaporative cooling Liquid desiccant dehumidification Response surface method System optimization |
Publisher: | Elsevier | Journal: | Journal of building engineering | EISSN: | 2352-7102 | DOI: | 10.1016/j.jobe.2023.107371 | Rights: | © 2023 Elsevier Ltd. All rights reserved. © 2023. This manuscript version is made available under the CC-BY-NC-ND 4.0 license https://creativecommons.org/licenses/by-nc-nd/4.0/ The following publication Zhang, Y., Zhang, H., Yang, H., Chen, Y., & Leung, C. W. (2023). Response surface modeling and optimization scheme of an internally cooled liquid desiccant air conditioning system. Journal of Building Engineering, 76, 107371 is available at https://doi.org/10.1016/j.jobe.2023.107371. |
| Appears in Collections: | Journal/Magazine Article |
Files in This Item:
| File | Description | Size | Format | |
|---|---|---|---|---|
| Zhang_Response_Surface_Modeling.pdf | Pre-Published version | 3.7 MB | Adobe PDF | View/Open |
Page views
58
Citations as of Nov 10, 2025
SCOPUSTM
Citations
15
Citations as of Dec 5, 2025
WEB OF SCIENCETM
Citations
14
Citations as of Dec 4, 2025
Google ScholarTM
Check
Altmetric
Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.