Title: A novel indirect evaporative cooler with porous media under dual spraying modes : a comparative analysis from energy, exergy, and environmental perspectives
Authors: Shi, W 
Yang, H 
Ma, X 
Liu, X
Issue Date: 1-Oct-2023
Source: Journal of building engineering, 1 Oct. 2023, v. 76, 106874
Abstract: Indirect evaporative cooling (IEC), which cools the air through the physical process, is regarded as one of the high-efficient air conditioning (AC) technology. The reliable performance of traditional IEC is maintained by consistent water spraying, consuming much energy and hindering further performance improvement. In this regard, we proposed a novel indirect evaporative cooler with porous media on the secondary air channel (PIEC) to mitigate the dependence on water spraying. For the PIEC, the water storage capacity of porous media enables periodic spraying. However, the performance comparison between periodic spraying and traditional consistent spraying is rarely carried out although the two modes have been achieved, which promotes this research. In this study, the PIEC model with consistent spraying and periodic spraying was briefly described based on our previous results. According to the results from the established model, the PIEC performance was analyzed and compared under dual spraying modes from the energy, exergy, and environmental (3E) perspectives. It is demonstrated that periodic spraying can significantly improve the system COP by 58.7% at the cost of tiny temperature fluctuations. Additionally, the periodic mode can increase the exergy efficiency and lessen the exergy loss ratio in the studied cases. Eventually, the PIEC system using periodic spraying can annually reduce up to 24.2% of CO2 emissions compared with the traditional consistent mode, indicating better environmental benefits.
Keywords: 3E evaluation
Air conditioning
Dual-mode spraying plan
Indirect evaporative cooling
Porous material
Publisher: Elsevier
Journal: Journal of building engineering 
EISSN: 2352-7102
DOI: 10.1016/j.jobe.2023.106874
Rights: © 2023 Elsevier Ltd. All rights reserved.
© 2023. This manuscript version is made available under the CC-BY-NC-ND 4.0 license https://creativecommons.org/licenses/by-nc-nd/4.0/
The following publication Shi, W., Yang, H., Ma, X., & Liu, X. (2023). A novel indirect evaporative cooler with porous media under dual spraying modes: A comparative analysis from energy, exergy, and environmental perspectives. Journal of Building Engineering, 76, 106874 is available at https://doi.org/10.1016/j.jobe.2023.106874.
Appears in Collections:Journal/Magazine Article

Files in This Item:
File Description SizeFormat 
Shi_Novel_Indirect_Evaporative.pdfPre-Published version2.58 MBAdobe PDFView/Open
Open Access Information
Status open access
File Version Final Accepted Manuscript
Access
View full-text via PolyU eLinks SFX Query
Show full item record

Page views

59
Citations as of Nov 10, 2025

SCOPUSTM   
Citations

27
Citations as of Dec 5, 2025

WEB OF SCIENCETM
Citations

25
Citations as of Dec 4, 2025

Google ScholarTM

Check

Altmetric


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.