Abstract: Previous studies on inter-unit dispersion are limited to isolated buildings. The influence of an upstream interfering building may significantly modify the indoor airflow characteristics of the wind-induced natural ventilated downstream interfered building. Motivated by the findings in previous studies, namely that infectious respiratory aerosols exhausted from a unit can re-enter into another unit in the same building through building envelope openings, this study investigates the inter-unit pollutant dispersion around a multi-story building in two wind directions by employing the computational fluid dynamics (CFD) method. The CFD model employed in this study has been validated against previous experimental data. The results show that the presence of an upstream building greatly changes the path lines around the downstream target building and the pollutant transportation routes around it. The presence of a low upstream building also greatly increases the average air exchange rate (ACH) values and the pollutant re-entry ratios (Rk) below the source unit on the windward side of the downstream target building for normal wind incidence. However, the presence of a high upstream building greatly increases the average ACH values on the windward side and increases the Rk on the leeward side of the downstream building for oblique wind incidence.
Keywords: CFD
Inter-unit dispersion
Natural ventilation
Upstream building
Wind directions
Publisher: Elsevier
Journal: Journal of wind engineering and industrial aerodynamics 
ISSN: 0167-6105
EISSN: 1872-8197
DOI: 10.1016/j.jweia.2016.01.007
Rights: © 2016 Elsevier Ltd. All rights reserved.
© 2016. This manuscript version is made available under the CC-BY-NC-ND 4.0 license https://creativecommons.org/licenses/by-nc-nd/4.0/.
The following publication Cui, D. J., Mak, C. M., Kwok, K. C. S., & Ai, Z. T. (2016). CFD simulation of the effect of an upstream building on the inter-unit dispersion in a multi-story building in two wind directions. Journal of Wind Engineering and Industrial Aerodynamics, 150, 31-41 is available at https://doi.org/10.1016/j.jweia.2016.01.007.
Appears in Collections:Journal/Magazine Article

Files in This Item:
File Description SizeFormat 
Mak_CFD_Simulation_Effect.pdfPre-Published version4.79 MBAdobe PDFView/Open
Open Access Information
Status open access
File Version Final Accepted Manuscript
Access
View full-text via PolyU eLinks SFX Query
Show full item record

Page views

119
Last Week
6
Last month
Citations as of Nov 9, 2025

Downloads

84
Citations as of Nov 9, 2025

SCOPUSTM   
Citations

48
Citations as of Dec 19, 2025

WEB OF SCIENCETM
Citations

43
Citations as of Dec 18, 2025

Google ScholarTM

Check

Altmetric


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.