Abstract: The indirect evaporative cooler (IEC) is a low-carbon device which cools the air with water evaporation. Its performances in dry regions have been investigated intensively. However, its application in hot and humid regions, where the IEC is used as a pre-cooling device in an air-conditioning system, is still at developing stage. The exhausted air from air-conditioned space is humidified and used as secondary air to pre-cool the fresh air. As the dew point temperature of the fresh air is high, condensation may occur in the dry channels. However, the parameter sensitivity analysis of IEC with condensation is lacking. Besides, the optimized IEC configuration may be different from that of dry regions because of distinguished air handling process. So the sensitivity analysis among seven parameters by orthogonal test was conducted based on the experimental-validated IEC model emphasizing on condensation condition. The optimization was then conducted to the most influential and engineering controllable parameters. The results indicate the channel gap and cooler height are the key influential factors on IEC thermal performance. The optimized channel gap is 2–3 mm and 3–4 mm under condensation and non-condensation state, respectively. The optimized NTUp is 4–7 and 3–5, respectively.
Keywords: Condensation
Indirect evaporative cooler
Optimization
Orthogonal test
Sensitivity analysis
Publisher: Pergamon Press
Journal: Applied energy 
ISSN: 0306-2619
EISSN: 1872-9118
DOI: 10.1016/j.apenergy.2016.06.121
Rights: © 2016 Elsevier Ltd. All rights reserved.
© 2016. This manuscript version is made available under the CC-BY-NC-ND 4.0 license https://creativecommons.org/licenses/by-nc-nd/4.0/.
The following publication Chen, Y., Yang, H., & Luo, Y. (2017). Parameter sensitivity analysis and configuration optimization of indirect evaporative cooler (IEC) considering condensation. Applied Energy, 194, 440-453 is available at https://doi.org/10.1016/j.apenergy.2016.06.121.
Appears in Collections:Journal/Magazine Article

Files in This Item:
File Description SizeFormat 
Chen_Parameter_Sensitivity_Analysis.pdfPre-Published version1.45 MBAdobe PDFView/Open
Open Access Information
Status open access
File Version Final Accepted Manuscript
Access
View full-text via PolyU eLinks SFX Query
Show full item record

Page views

71
Last Week
3
Last month
Citations as of Nov 9, 2025

Downloads

98
Citations as of Nov 9, 2025

SCOPUSTM   
Citations

87
Citations as of Dec 19, 2025

WEB OF SCIENCETM
Citations

83
Citations as of Dec 18, 2025

Google ScholarTM

Check

Altmetric


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.