Please use this identifier to cite or link to this item: http://hdl.handle.net/10397/102901
PIRA download icon_1.1View/Download Full Text
Title: Adaptive full-range decoupled ventilation strategy and air-conditioning systems for cleanrooms and buildings requiring strict humidity control and their performance evaluation
Authors: Zhuang, C 
Wang, S 
Shan, K 
Issue Date: 1-Feb-2019
Source: Energy, 1 Feb. 2019, v. 168, p. 883-896
Abstract: The air-conditioning systems in buildings and spaces, such as cleanrooms, requiring strict space humidity control are usually energy intensive, where significant energy wastes often occur due to improper system design and control. Dedicated outdoor air ventilation strategy, as the most recommended solution today, offers good energy performance by fully decoupling the cooling and dehumidification process. But its energy saving potential is restricted to a range of working conditions, due to the excessive outdoor air intake, it cannot provide energy-efficient operation when the internal latent load and ambient enthalpy are high. This paper therefore proposes a novel “adaptive full-range decoupled ventilation strategy”, which offers optimized energy-efficient operation by incorporating the advantages of different ventilation strategies and adopting an adaptive economizer. This study also addresses the design of the air-conditioning systems for the implementation of the proposed ventilation strategy. The energy performance and economic analysis of the air-conditioning systems adopting the proposed ventilation strategy are investigated and compared with most updated strategies available. Results show that the proposed ventilation strategy can offer superior energy performance over the full range of internal load and weather conditions while the initial cost is even lower than that for the most recommended ventilation strategy today.
Keywords: Adaptive full-range decoupled ventilation
Air-conditioning system
Dedicated ventilation
Energy conservation
Strict humidity control
Publisher: Pergamon Press
Journal: Energy 
ISSN: 0360-5442
EISSN: 1873-6785
DOI: 10.1016/j.energy.2018.11.147
Rights: © 2018 Elsevier Ltd. All rights reserved.
© 2018. This manuscript version is made available under the CC-BY-NC-ND 4.0 license https://creativecommons.org/licenses/by-nc-nd/4.0/.
The following publication Zhuang, C., Wang, S., & Shan, K. (2019). Adaptive full-range decoupled ventilation strategy and air-conditioning systems for cleanrooms and buildings requiring strict humidity control and their performance evaluation. Energy, 168, 883-896 is available at https://doi.org/10.1016/j.energy.2018.11.147.
Appears in Collections:Journal/Magazine Article

Files in This Item:
File Description SizeFormat 
Zhuang_Adaptive_Full-range_Decoupled.pdfPre-Published version5.73 MBAdobe PDFView/Open
Open Access Information
Status open access
File Version Final Accepted Manuscript
Access
View full-text via PolyU eLinks SFX Query
Show full item record

Page views

123
Last Week
4
Last month
Citations as of Nov 9, 2025

Downloads

112
Citations as of Nov 9, 2025

SCOPUSTM   
Citations

39
Citations as of Dec 19, 2025

WEB OF SCIENCETM
Citations

32
Citations as of Dec 18, 2025

Google ScholarTM

Check

Altmetric


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.