Please use this identifier to cite or link to this item: http://hdl.handle.net/10397/101631
PIRA download icon_1.1View/Download Full Text
Title: Impact of indoor heat load and natural ventilation on thermal comfort of radiant cooling system : an experimental study
Authors: Dharmasastha, K 
Samuel, DGL
Nagendra, SMS
Maiya, MP
Issue Date: Oct-2023
Source: Energy and Built Environment, Oct 2023, v. 4, no. 5, p. 543-556
Abstract: Construction and operation of buildings are responsible for about 20% of the global energy consumption. The embodied energy of conventional buildings is high due to the utilization of energy-intensive construction materials and traditional construction methodology. Higher operational energy is attributed to the usage of power-consuming conventional air-conditioning systems. Therefore, moving to an energy-efficient cooling technology and eco-friendly building material can lead to significant energy savings and CO2 emission reduction. In the present study, an energy-efficient thermally activated building system (TABS) is integrated with glass fiber reinforced gypsum (GFRG), an eco-friendly building material. The proposed hybrid system is termed the thermally activated glass fiber reinforced gypsum (TAGFRG) system. This system is not only energy-efficient and eco-friendly but also provides better thermal comfort. An experimental room with a TAGFRG roof is constructed on the premises of the Indian Institute of Technology Madras (IITM), Chennai, located in a tropical wet and dry climate zone. The influence of indoor sensible heat load and the impact of natural ventilation on the thermal comfort of the TAGFRG system are investigated. An increase in internal heat load from 400 to 700 W deteriorates the thermal comfort of the indoor space. This is evident from the increases in operative temperatures from 29.8 to 31.5 °C and the predicted percentage of dissatisfaction from 44.5% to 80.9%. Natural ventilation increases the diurnal fluctuation of indoor air temperature by 1.6 and 1.9 °C for with and without cooling cases, respectively. It reduces the maximum indoor CO2 concentration from 912 to 393 ppm.
Keywords: Air-conditioning
Indoor air quality
Natural ventilation
Thermal comfort
Thermally activated building system
Publisher: Ke Ai Publishng Communications Ltd.
Journal: Energy and built environment 
EISSN: 2666-1233
DOI: 10.1016/j.enbenv.2022.04.003
Rights: ©2022 Southwest Jiatong University. Publishing services by Elsevier B.V. on behalf of KeAi Communication Co. Ltd. This is an open access article under the CC BY-NC-ND license (http://creativecommons.org/licenses/by-nc-nd/4.0/).
The following publication Dharmasastha, K., Samuel, D. L., Nagendra, S. S., & Maiya, M. P. (2023). Impact of indoor heat load and natural ventilation on thermal comfort of radiant cooling system: An experimental study. Energy and Built Environment, 4(5), 543-556 is available at https://doi.org/10.1016/j.enbenv.2022.04.003.
Appears in Collections:Journal/Magazine Article

Files in This Item:
File Description SizeFormat 
1-s2.0-S2666123322000319-main.pdf4.38 MBAdobe PDFView/Open
Open Access Information
Status open access
File Version Version of Record
Access
View full-text via PolyU eLinks SFX Query
Show full item record

Page views

71
Citations as of May 11, 2025

Downloads

79
Citations as of May 11, 2025

SCOPUSTM   
Citations

15
Citations as of May 15, 2025

Google ScholarTM

Check

Altmetric


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.