Title: DC fault detection in MTDC systems based on transient high frequency of current
Authors: Li, Y 
Wu, L
Li, J
Xiong, L 
Zhang, X 
Song, G
Xu, Z 
Issue Date: Jun-2019
Source: IEEE transactions on power delivery, June 2019, v. 34, no. 3, p. 950-962
Abstract: Isolation of the fault dc lines during the initial short period after fault is a major challenge in the multi-terminal dc (MTDC) system based on a voltage-source converter (VSC). Existing protection schemes are mainly designed based on the numerical simulations, which lacks the theoretical analysis. In this paper, a high-frequency equivalent model of a VSC-based MTDC system is first proposed for the fault current calculation. Based on the dc fault analysis, it is validated that the high-frequency fault current components flow in the fault line and then dramatically decay in the healthy line. Accordingly, a novel dc fault detection method for the VSC-based MTDC system is proposed. In the proposed approach, the primary protection utilizes the transient high-frequency energy of line current and the fault line can be identified quickly without communication. In addition, the influence of the transient traveling-wave appearing on the long-transmission line on the proposed protection scheme is also investigated. Numerous simulation studies carried out in PSCAD/EMTDC have demonstrated that the proposed high-frequency equivalent model can be utilized for the initial dc fault analysis of the VSC-based MTDC system and the proposed protection scheme is effective in different time windows, different fault locations, and high fault resistances. Compared with the existing rate of change of current-based protection scheme, the proposed primary protection requires relatively low sampling frequency, is insensitive to the parameter changes, and has high robustness with respect to the outside noises and data missing.
Keywords: Fault analysis
High frequency equivalent model
Transient high-frequency current
VSC based MTDC
Publisher: Institute of Electrical and Electronics Engineers
Journal: IEEE transactions on power delivery 
ISSN: 0885-8977
EISSN: 1937-4208
DOI: 10.1109/TPWRD.2018.2882431
Rights: © 2018 IEEE. Personal use of this material is permitted. Permission from IEEE must be obtained for all other uses, in any current or future media, including reprinting/republishing this material for advertising or promotional purposes, creating new collective works, for resale or redistribution to servers or lists, or reuse of any copyrighted component of this work in other works.
The following publication Y. Li et al., "DC Fault Detection in MTDC Systems Based on Transient High Frequency of Current," in IEEE Transactions on Power Delivery, vol. 34, no. 3, pp. 950-962, June 2019 is available at https://doi.org/10.1109/TPWRD.2018.2882431.
Appears in Collections:Journal/Magazine Article

Files in This Item:
File Description SizeFormat 
Li_DC_Fault_Detection.pdfPre-Published version1.09 MBAdobe PDFView/Open
Open Access Information
Status open access
File Version Final Accepted Manuscript
Access
View full-text via PolyU eLinks SFX Query
Show full item record

Page views

84
Citations as of Apr 14, 2025

Downloads

74
Citations as of Apr 14, 2025

SCOPUSTM   
Citations

93
Citations as of Sep 12, 2025

WEB OF SCIENCETM
Citations

65
Citations as of Oct 10, 2024

Google ScholarTM

Check

Altmetric


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.