Title: Numerical and experimental investigations on thermal management for data center with cold aisle containment configuration
Authors: Lee, YT
Wen, CY 
Shih, YC
Li, Z 
Yang, AS
Issue Date: 1-Feb-2022
Source: Applied energy, 1 Feb. 2022, v. 307, 118213
Abstract: This study proposes the container data center with the featured cold aisle containment (CAC) as effective thermal control strategy. In design, the overhead downward flow system is implemented with a heat exchanger arranged right above the data center on the air side and an evaporative water chiller on the water side to form the cooling approach. The cold airflows and hot exhausts of racks are separately transported by the contained cold and hot aisles to alleviate the problem of cold and hot air mixing. The measurements of air temperature and velocity of racks are used to validate the prediction accuracy of the computational fluid dynamics (CFD) model. The performance metrics in terms of the rack cooling index (RCI), return temperature index (RTI), supply heat index (SHI) are used to examine the design effectiveness of the proposed test data center. The simulations are then extended to assess the air distribution and thermal management at varied supply air temperatures and velocities for a large-scale data center to be built in the green energy technology demonstration site of the Shalun smart green energy science city. Overall, the calculated average PUE of 1.38 for the large-scale data center is notably less than the average PUE of 1.59 from the results of 2020 data center industry survey, indicating the potential savings of cooling energy and cost. This paper demonstrates a generalized approach as an easily adaptable, cost-effective solution for data centers to be deployed in tropical and subtropical areas.
Keywords: Airflow management
CFD simulation
Data center
Rack cooling index
Return temperature index
Supply heat index
Publisher: Pergamon Press
Journal: Applied energy 
ISSN: 0306-2619
EISSN: 1872-9118
DOI: 10.1016/j.apenergy.2021.118213
Rights: © 2021 Elsevier Ltd. All rights reserved.
© 2021. This manuscript version is made available under the CC-BY-NC-ND 4.0 license http://creativecommons.org/licenses/by-nc-nd/4.0/.
The following publication Lee, Y.-T., Wen, C.-Y., Shih, Y.-C., Li, Z., & Yang, A.-S. (2022). Numerical and experimental investigations on thermal management for data center with cold aisle containment configuration. Applied Energy, 307, 118213 is available at https://dx.doi.org/10.1016/j.apenergy.2021.118213.
Appears in Collections:Journal/Magazine Article

Files in This Item:
File Description SizeFormat 
Lee_Numerical_Experimental_Thermal.pdfPre-Published version7.52 MBAdobe PDFView/Open
Open Access Information
Status open access
File Version Final Accepted Manuscript
Access
View full-text via PolyU eLinks SFX Query
Show full item record

Page views

90
Last Week
4
Last month
Citations as of Mar 24, 2024

Downloads

2
Citations as of Mar 24, 2024

SCOPUSTM   
Citations

14
Citations as of Mar 29, 2024

WEB OF SCIENCETM
Citations

13
Citations as of Mar 28, 2024

Google ScholarTM

Check

Altmetric


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.