Title: Indirect evaporative cooling maps of China : optimal and quick performance identification based on a data-driven model
Authors: Shi, W 
Ma, X 
Gu, Y
Min, Y
Yang, H 
Issue Date: 15-Sep-2022
Source: Energy conversion and management, 15 Sept 2022, v. 268, 116047
Abstract: The data-driven models of various air conditioning (AC) systems have been developed because of the wider application of machine learning in the engineering field. Indirect evaporative cooler (IEC), known as one of the effective and environment-friendly AC devices, achieves the cooling purpose without using any types of mechanical compressors or chemical refrigerants. Recent studies on various IECs have been carried out in full swing with a large amount of valuable data produced. However, the data-driven model of the cross-flow IEC for sensible and total cooling is yet to be developed. In addition, by extracting the indoor cold exhaust air into the secondary air channel, the application range of an IEC can be extended, but so far the performance of IEC used in different regions has been rarely evaluated. In this study, an IEC model was established based on the artificial neural network (ANN), which was validated with on-site measurement results from a real engineering project. Combining the selected geometric size of IEC and various outdoor weather conditions into the IEC-ANN model, a case study was conducted to present the annual and seasonal IEC performance maps of China, and the optimal application regions could be determined. Results show that south China, east China, and middle China are more suitable to employ IEC for air treatment and energy saving. In south China, the greatest average temperature drop caused by the IEC is 4.52 ℃. The maximum cooling capacity can reach 5.74 kW, and it accounts for 30.1 % of the total cooling load. In the typical office building, the seasonal energy saving of the IEC with the given size is up to 3.64 kWh/m2, and the annual energy saving can reach 6.02 kWh/m2. In addition, the inference time of this IEC-ANN model was significantly shorter compared with a numerical model. Based on the quick prediction speed, the model can improve the working efficiency in the design stage of the engineering and may provide a swift response to guide the system operation.
Keywords: Air conditioning
Data-driven model
Indirect evaporative cooling
Cooling map
Optimal and quick identification
Publisher: Elsevier Ltd
Journal: Energy conversion and management 
ISSN: 0196-8904
EISSN: 1879-2227
DOI: 10.1016/j.enconman.2022.116047
Rights: © 2022 Elsevier Ltd. All rights reserved.
© 2022. This manuscript version is made available under the CC-BY-NC-ND 4.0 license http://creativecommons.org/licenses/by-nc-nd/4.0/.
The following publication Shi, W., Ma, X., Gu, Y., Min, Y., & Yang, H. (2022). Indirect evaporative cooling maps of China: Optimal and quick performance identification based on a data-driven model. Energy Conversion and Management, 268, 116047 is available at https://dx.doi.org/10.1016/j.enconman.2022.116047.
Appears in Collections:Journal/Magazine Article

Files in This Item:
File Description SizeFormat 
Shi_Indirect_Evaporative_Cooling.pdfPre-Published version2.41 MBAdobe PDFView/Open
Open Access Information
Status open access
File Version Final Accepted Manuscript
Access
View full-text via PolyU eLinks SFX Query
Show full item record

Page views

93
Citations as of Nov 10, 2025

Downloads

66
Citations as of Nov 10, 2025

SCOPUSTM   
Citations

16
Citations as of Dec 19, 2025

WEB OF SCIENCETM
Citations

12
Citations as of Sep 26, 2024

Google ScholarTM

Check

Altmetric


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.