Please use this identifier to cite or link to this item: http://hdl.handle.net/10397/98927
PIRA download icon_1.1View/Download Full Text
Title: Short-circuit modeling of DFIG-based WTG in sequence domain considering various fault- ride- through requirements and solutions
Authors: Chang, Y 
Kocar, I 
Farantatos, E
Haddadi, A
Patel, M
Issue Date: Jun-2023
Source: IEEE transactions on power delivery, June 2023, v. 38, no. 3, p. 2088-2100
Abstract: The doubly fed induction generator (DFIG) based wind turbine generator (WTG) can activate different fault ride through (FRT) control schemes and circuits to comply with various grid code or utility interconnection requirements. These FRT solutions play a key role in the resulting fault current of the DFIG-based WTG as well as the voltages and currents distributed in faulted networks. This paper accounts for their impact by proposing a new generic sequence domain model of the DFIG-based WTG for static short circuit calculations. In this paper, the FRT configurations are classified into three types. The proposed model first calculates the positive- and negative-sequence current phasors under the specified FRT control. Then based on the control, the desired currents and voltages are calculated by explicit equations to determine whether the crowbar could operate during FRT operation. By comparing with detailed electromagnetic transient (EMT) simulations using an EPRI benchmark system, the proposed model, incorporated into an iterative steady state solver, is shown to be accurate to calculate voltage and current phasors in an efficient manner. The proposed model provides a rapid tool for short circuit computations and protective relaying studies considering various grid code requirements and FRT implementations.
Keywords: Doubly fed induction generator (DFIG)
Short circuit
Wind turbine generator
Protection systems
Publisher: Institute of Electrical and Electronics Engineers
Journal: IEEE transactions on power delivery 
ISSN: 0885-8977
EISSN: 1937-4208
DOI: 10.1109/TPWRD.2023.3235985
Rights: © 2023 IEEE. Personal use of this material is permitted. Permission from IEEE must be obtained for all other uses, in any current or future media, including reprinting/republishing this material for advertising or promotional purposes, creating new collective works, for resale or redistribution to servers or lists, or reuse of any copyrighted component of this work in other works.
The following publication Y. Chang, I. Kocar, E. Farantatos, A. Haddadi and M. Patel, "Short-Circuit Modeling of DFIG-Based WTG in Sequence Domain Considering Various Fault- Ride-Through Requirements and Solutions," in IEEE Transactions on Power Delivery, vol. 38, no. 3, pp. 2088-2100, June 2023 is available at https://doi.org/10.1109/TPWRD.2023.3235985.
Appears in Collections:Journal/Magazine Article

Files in This Item:
File Description SizeFormat 
Chang_Short-Circuit_Modeling_DFIG-Based.pdfPre-Published version1.37 MBAdobe PDFView/Open
Open Access Information
Status open access
File Version Final Accepted Manuscript
Access
View full-text via PolyU eLinks SFX Query
Show full item record

Page views

79
Citations as of Apr 14, 2025

Downloads

136
Citations as of Apr 14, 2025

SCOPUSTM   
Citations

12
Citations as of Jun 21, 2024

WEB OF SCIENCETM
Citations

11
Citations as of Oct 10, 2024

Google ScholarTM

Check

Altmetric


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.