Title: The impact of DFIG control schemes on the negative-sequence based differential protection
Authors: Chang, Y
Zhao, M
Kocar, I 
Issue Date: Oct-2022
Source: Electric power systems research, Oct. 2022, v. 211, 108564
Abstract: Negative-sequence currents at the transmission line terminals are widely adopted in differential protection to achieve excellent sensitivity. The underlying principle is that the traditional power sources (synchronous generators) can be treated as inductive reactance in the negative-sequence network. However, for the transmission lines connected to Doubly-Fed Induction Generator (DFIG) based wind parks (WPs), the negative-sequence currents are controlled by fault-ride-through (FRT) solutions. This paper first analyzes the phasor characteristics between negative-sequence voltage and current of a DFIG-based WP under three typical FRT solutions, and then evaluates their impact on the dynamic performance of negative-sequence differential protection elements (87LQ). The analysis indicates that a certain FRT control strategy would make DFIG-based WP provide capacitive current into the negative-sequence network. This impacts the sensitivity and even results in maloperation as shown for the first time in this work. The analytical results are validated with detailed time domain models and simulations in Simulink.
Keywords: Doubly fed induction generator (DFIG)
Differential protection
Negative sequence
Short circuit
Unsymmetrical fault
Publisher: Elsevier
Journal: Electric power systems research 
ISSN: 0378-7796
EISSN: 1873-2046
DOI: 10.1016/j.epsr.2022.108564
Rights: © 2022 Published by Elsevier B.V.
© 2022. This manuscript version is made available under the CC-BY-NC-ND 4.0 license https://creativecommons.org/licenses/by-nc-nd/4.0/
The following publication Chang, Y., Zhao, M., & Kocar, I. (2022). The impact of DFIG control schemes on the negative-sequence based differential protection. Electric Power Systems Research, 211, 108564 is available at https://doi.org/10.1016/j.epsr.2022.108564
Appears in Collections:Journal/Magazine Article

Files in This Item:
File Description SizeFormat 
Chang_Impact_DFIG_Control.pdfPre-Published version1.85 MBAdobe PDFView/Open
Open Access Information
Status open access
File Version Final Accepted Manuscript
Access
View full-text via PolyU eLinks SFX Query
Show full item record

Page views

79
Citations as of Apr 14, 2025

Downloads

13
Citations as of Apr 14, 2025

SCOPUSTM   
Citations

7
Citations as of Jun 21, 2024

WEB OF SCIENCETM
Citations

9
Citations as of Oct 31, 2024

Google ScholarTM

Check

Altmetric


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.