Title: Polymeric insulator conditions estimation by using leakage current characteristics based on simulation and experimental investigation
Authors: Salem, AA
Lau, KY
Abdul-Malek, Z
Mohammed, N
Al-Shaalan, AM
Al-Shamma’a, AA
Farh, HMH 
Issue Date: Feb-2022
Source: Polymers, Feb. 2022, v. 14, no. 4, 737
Abstract: The current work contributes an estimate of the time-frequency characteristics of a leakage current in assessing the health condition of a polluted polymeric insulator. A 33 kV polymer insulator string was subjected to a series of laboratory tests under a range of environmental conditions, including pollution, wetting rate (WR), non-soluble deposit density (NSDD), and non-uniform distribution pollution (FT/B). The temporal and frequency features of the leakage current were then extracted and used as assessment indicators for insulator conditions based on laboratory test find-ings. Two indices were generated from the leakage current waveform in the time domain: the curve slope index (F1), which is determined by measuring the inclination of the curve between two suc-cessive time peaks of the leakage current, and the crest factor indicator (F2). The frequency domain of the leakage current signal was used to calculate the other two indices. These are the odd harmonic indicators derived from the odd frequency harmonics of the leakage current up to the 9th component (F3) and the 5th to 3rd harmonics ratio (F4). The findings showed that the suggested indicators were capable of evaluating insulator conditions. Finally, the confusion matrix for the experimental and prediction results obtained with the proposed indices was used to assess which indicator per-formed the best. Therefore, the analysis suggests an alternative and effective method for estimating the health condition of a polluted insulator through leakage current characteristics obtained in the time and frequency domains.
Keywords: Leakage current indices
Pollution
Polymer insulator
Prediction
Publisher: Molecular Diversity Preservation International (MDPI)
Journal: Polymers 
ISSN: 2073-4360
DOI: 10.3390/polym14040737
Rights: © 2022 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https://creativecommons.org/licenses/by/4.0/).
The following publication Salem, A. A., Lau, K. Y., Abdul-Malek, Z., Mohammed, N., Al-Shaalan, A. M., Al-Shamma’a, A. A., & Farh, H. M. (2022). Polymeric Insulator Conditions Estimation by Using Leakage Current Characteristics Based on Simulation and Experimental Investigation. Polymers, 14(4), 737 is available at https://doi.org/10.3390/polym14040737.
Appears in Collections:Journal/Magazine Article

Files in This Item:
File Description SizeFormat 
polymers-14-00737-v2.pdf40.13 MBAdobe PDFView/Open
Open Access Information
Status open access
File Version Version of Record
Access
View full-text via PolyU eLinks SFX Query
Show full item record

Page views

33
Last Week
1
Last month
Citations as of Sep 22, 2024

Downloads

19
Citations as of Sep 22, 2024

SCOPUSTM   
Citations

11
Citations as of Sep 26, 2024

WEB OF SCIENCETM
Citations

8
Citations as of Jun 20, 2024

Google ScholarTM

Check

Altmetric


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.