Please use this identifier to cite or link to this item: http://hdl.handle.net/10397/96176
PIRA download icon_1.1View/Download Full Text
Title: Analysis of the grounding for the substation under very fast transient using improved lossy thin-wire model for FDTD
Authors: Chen, H 
Du, Y 
Yuan, M
Liu, QH
Issue Date: Dec-2018
Source: IEEE transactions on electromagnetic compatibility, Dec. 2018, v. 60, no. 6, p. 1833-1841
Abstract: A thin-wire model of conductors with arbitrary cross sections for a finite-difference time-domain (FDTD) method is proposed for the study of lightning transients in electrical systems. The proposed thin-wire model considers both the frequency-dependent characteristics of the wires and the influences of the surrounding media. The model represents a wire using four FDTD cells with an equivalent side length and modified material parameters. A rational equivalent circuit is added at the center edge of the FDTD cells to represent the internal impedance of the wire. An analytical formula for determining the equivalent side length and the modified material parameters of the FDTD cells are also presented. The proposed formula gives a new prospect to build the thin-wire model in FDTD. In this model, the equivalent side length can be set arbitrarily and much larger than the original wire, which can greatly reduce the computation time. Meanwhile, the method can be extended to the thin-wire structure with arbitrary cross sections. The model is verified with various measurements. Finally, a practical grounding grid of a substation with external water supply is analyzed.
Keywords: Finite-difference time domain (FDTD)
Grounding grid
Lightning
Skin effect
Substation
Publisher: Institute of Electrical and Electronics Engineers
Journal: IEEE transactions on electromagnetic compatibility 
ISSN: 0018-9375
EISSN: 1558-187X
DOI: 10.1109/TEMC.2018.2807123
Rights: © 2018 IEEE. Personal use of this material is permitted. Permission from IEEE must be obtained for all other uses, in any current or future media, including reprinting/republishing this material for advertising or promotional purposes, creating new collective works, for resale or redistribution to servers or lists, or reuse of any copyrighted component of this work in other works.
The following publication H. Chen, Y. Du, M. Yuan and Q. H. Liu, "Analysis of the Grounding for the Substation Under Very Fast Transient Using Improved Lossy Thin-Wire Model for FDTD," in IEEE Transactions on Electromagnetic Compatibility, vol. 60, no. 6, pp. 1833-1841, Dec. 2018 is available at https://doi.org/10.1109/TEMC.2018.2807123.
Appears in Collections:Journal/Magazine Article

Files in This Item:
File Description SizeFormat 
Chen_Analysis_Grounding_Substatiunder.pdfPre-Published version1.39 MBAdobe PDFView/Open
Open Access Information
Status open access
File Version Final Accepted Manuscript
Access
View full-text via PolyU eLinks SFX Query
Show full item record

Page views

61
Last Week
0
Last month
Citations as of Sep 22, 2024

Downloads

42
Citations as of Sep 22, 2024

SCOPUSTM   
Citations

9
Citations as of Sep 26, 2024

WEB OF SCIENCETM
Citations

10
Citations as of Sep 26, 2024

Google ScholarTM

Check

Altmetric


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.