Please use this identifier to cite or link to this item: http://hdl.handle.net/10397/95411
PIRA download icon_1.1View/Download Full Text
Title: Retrofitting building fire service water tanks as chilled water storage for power demand limiting
Authors: Yan, C 
Wang, S 
Fan, C 
Xiao, F 
Issue Date: Jan-2017
Source: Building services engineering research and technology, Jan. 2017, v. 38, no. 1, p. 47-63
Abstract: Peak demand cost usually contributes a large proportion of the total electricity bills in buildings. Using existing building facilities for power demand limiting has been verified as effective measures to reduce monthly peak demands and associated costs. Fire service water tanks exist in most commercial buildings. This paper presents a comprehensive study on how to effectively retrofit existing building fire service water tanks as chilled water storage for power demand limiting. Important technical and economic factors that may affect the implementation of the proposed retrofitting are addressed. Two retrofitting schemes, i.e. a small δT (storage temperature difference) scheme and a large δT scheme are proposed for integrating the chilled water storage system into an existing all-air system and an existing air-water air conditioning system, respectively. Two optimal demand limiting control strategies, i.e. time-based control and demand-based control, are proposed for maximizing the monthly peak demand reduction of buildings with regular and variable peak occurring time, respectively. The cost-effectiveness of different retrofitting schemes in three real buildings in Hong Kong is analysed. Results show that substantial cost savings can be achieved with short payback periods (0.7-2.6 years) for the retrofits in these three buildings.
Practical application: This paper presents a techno-economic analysis on retrofitting existing building fire service water tanks as chilled water storage for power demand limiting and operational cost saving. The proposed retrofitting schemes and demand limiting control strategies enable chilled water storage systems to be readily applied to most existing buildings. Building owners can benefit from the peak demand cost saving as the monthly peak demand can be significantly reduced by using chilled water storage. The extra costs involved in tank retrofits and system integrations can be paid back within three years.
Keywords: Air-conditioning system
Building retrofitting
Demand limiting
Fire tank
Thermal storage
Publisher: SAGE Publications
Journal: Building services engineering research and technology 
ISSN: 0143-6244
EISSN: 1477-0849
DOI: 10.1177/0143624416669553
Rights: This is the accepted version of the publication Yan C, Wang S, Fan C, Xiao F. Retrofitting building fire service water tanks as chilled water storage for power demand limiting. Building Services Engineering Research and Technology. 2017;38(1):47-63. © The Chartered Institution of Building Services Engineers 2016. DOI: 10.1177/0143624416669553
Appears in Collections:Journal/Magazine Article

Files in This Item:
File Description SizeFormat 
Wang_Retrofitting_Building_Fire.pdfPre-Published version1.74 MBAdobe PDFView/Open
Open Access Information
Status open access
File Version Final Accepted Manuscript
Access
View full-text via PolyU eLinks SFX Query
Show full item record

Page views

72
Last Week
0
Last month
Citations as of Sep 22, 2024

Downloads

78
Citations as of Sep 22, 2024

SCOPUSTM   
Citations

8
Citations as of Sep 26, 2024

WEB OF SCIENCETM
Citations

8
Citations as of Sep 26, 2024

Google ScholarTM

Check

Altmetric


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.