Title: Impact of inverter-based resources on negative sequence quantities-based protection elements
Authors: Haddadi, A
Zhao, M
Kocar, I 
Karaagac, U 
Chan, KW 
Farantatos, E
Issue Date: Feb-2021
Source: IEEE transactions on power delivery, Feb. 2021, v. 36, no. 1, 9022918, p. 289-298
Abstract: Inverter-Based Resources (IBRs), including Wind turbine generators (WTGs), exhibit substantially different negative-sequence fault current characteristics compared to synchronous generators (SGs). These differences may cause misoperation of customary negative-sequence-based protective elements set under the assumption of a conventional SG dominated power system. The amplitude of the negative-sequence fault current of a WTG is smaller than that of an SG. This may lead to misoperation of the negative-sequence overcurrent elements 50Q/51Q. Moreover, the angular relation of the negative-sequence current and voltage is different under WTGs, which may result in the misoperation of directional negative-sequence overcurrent element 67Q. This paper first studies the key differences between the WTGs and SG by comparing their equivalent negative-sequence impedances with SG's. Then, simulation case studies are presented showing the misoperation of 50Q and 67Q due to wind generation and the corresponding impact on communication-assisted protection and fault identification scheme (FID). The impact on directional element is also experimentally validated in a hardware-in-the-loop real-time simulation set up using a physical relay. Finally, the paper studies the impact of various factors such as WTG type (Type-III/Type-IV) and Type-IV WTG control scheme (coupled/decoupled sequence) to determine the key features that need to be considered in practical protection studies. The objective is to show potential protection misoperation issues, identify the cause, and propose potential solutions.
Keywords: Directional negative-sequence overcurrent
Doubly-fed induction generator
Full-size converter
Inverter-based resource
Negative sequence component
Negative-sequence overcurrent protection
Power system modeling
Power system protection
Wind farms
Publisher: Institute of Electrical and Electronics Engineers
Journal: IEEE transactions on power delivery 
ISSN: 0885-8977
EISSN: 1937-4208
DOI: 10.1109/TPWRD.2020.2978075
Rights: © 2020 IEEE. Personal use of this material is permitted. Permission from IEEE must be obtained for all other uses, in any current or future media, including reprinting/republishing this material for advertising or promotional purposes, creating new collective works, for resale or redistribution to servers or lists, or reuse of any copyrighted component of this work in other works.
The following publication A. Haddadi, M. Zhao, I. Kocar, U. Karaagac, K. W. Chan and E. Farantatos, "Impact of Inverter-Based Resources on Negative Sequence Quantities-Based Protection Elements," in IEEE Transactions on Power Delivery, vol. 36, no. 1, pp. 289-298, Feb. 2021 is available at https://doi.org/10.1109/TPWRD.2020.2978075
Appears in Collections:Journal/Magazine Article

Files in This Item:
File Description SizeFormat 
Karaagac_Impact_Inverter-Based_Resources.pdfPre-Published version1.55 MBAdobe PDFView/Open
Open Access Information
Status open access
File Version Final Accepted Manuscript
Access
View full-text via PolyU eLinks SFX Query
Show full item record

Page views

62
Last Week
0
Last month
Citations as of May 5, 2024

Downloads

123
Citations as of May 5, 2024

SCOPUSTM   
Citations

77
Citations as of Apr 26, 2024

WEB OF SCIENCETM
Citations

52
Citations as of May 2, 2024

Google ScholarTM

Check

Altmetric


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.