Please use this identifier to cite or link to this item: http://hdl.handle.net/10397/108137
PIRA download icon_1.1View/Download Full Text
Title: Feasibility analysis of indirect evaporative cooling system assisted by liquid desiccant for data centers in hot-humid regions
Authors: Shi, W 
Ma, X 
Min, Y
Yang, H 
Issue Date: Mar-2024
Source: Sustainability, Mar. 2024, v. 16, no. 5, 2011
Abstract: The rapid development of data centers (DCs) has led to a marked increase in energy consumption in recent years, which poses a direct challenge to global efforts aimed at reducing carbon emissions. In regions with hot and humid climates, the energy demand is largely driven by air conditioning systems necessarily to maintain appropriate operational temperatures. This study proposes a novel multi-stage indirect evaporative cooling (IEC) system, incorporating a liquid desiccant in the primary air channel to address the cooling demands of such DCs. Our approach involves a two-stage process where the first stage uses a liquid desiccant-based IEC (LD-IEC) for air dehumidification and the second stage utilizes the treated air from the first stage as the secondary air to enhance the cooling effect. A simulation model of the proposed system is established with validation, and the performance of the multi-stage system was also discussed based on different operation modes. Furthermore, a case study was conducted to investigate the feasibility of using this system in the DC under a typical hot and humid zone. The findings reveal that the first-stage LD-IEC is capable of diminishing the wet-bulb temperature of the ambient air. Furthermore, the case study demonstrates that the proposed system can greatly improve the temperature drop by 72.7% compared to the single IEC, which noticeably reduces the operation time of energy-intensive supplementary cooling equipment from 5092 h to 31 h given the supply air temperature threshold of 25 °C. In summary, the proposed system could substantially decrease reliance on traditional cooling systems, which demonstrates a promising avenue to fully use this passive cooling technology for cooling DCs.
Keywords: Air conditioning
Data center
Indirect evaporative cooling
Liquid desiccant
Publisher: Molecular Diversity Preservation International (MDPI)
Journal: Sustainability 
EISSN: 2071-1050
DOI: 10.3390/su16052011
Rights: © 2024 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https://creativecommons.org/licenses/by/4.0/).
The following publication Shi,W.; Ma, X.; Min, Y.; Yang, H. Feasibility Analysis of Indirect Evaporative Cooling System Assisted by Liquid Desiccant for Data Centers in Hot-Humid Regions. Sustainability 2024, 16, 2011 is available at https://doi.org/10.3390/su16052011.
Appears in Collections:Journal/Magazine Article

Files in This Item:
File Description SizeFormat 
sustainability-16-02011.pdf2.74 MBAdobe PDFView/Open
Open Access Information
Status open access
File Version Version of Record
Access
View full-text via PolyU eLinks SFX Query
Show full item record

Page views

62
Citations as of Apr 14, 2025

Downloads

10
Citations as of Apr 14, 2025

SCOPUSTM   
Citations

6
Citations as of Sep 12, 2025

WEB OF SCIENCETM
Citations

2
Citations as of Nov 14, 2024

Google ScholarTM

Check

Altmetric


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.