Title: Improving the performance of indirect evaporative cooler for energy recovery from the perspective of nozzle configuration : a CFD model analysis
Authors: Ma, X 
Shi, W 
Yang, H 
Issue Date: 1-Oct-2023
Source: Journal of building engineering, 1 Oct. 2023, v. 76, 107195
Abstract: As a sustainable cooling technology, indirect evaporative cooling (IEC) has been widely recognized as an effective means of achieving carbon neutrality based on its low energy consumption and high efficiency in central air conditioning (AC) systems of buildings. In contrast to the conventional arrangement, IECs as heat recovery units are often arranged in a diamond shape inside the air handling units (AHUs) of data centers (DCs), an approach that facilitates the flexible use of space and integration within the units in a more compact form. The use of CFD simulations allows an integrated analysis of the coupling of hydrodynamic, thermal and mass properties helps to improve the evaporation performance of IECs. In this study, a 3D simulation model of a diamond-shaped IEC containing the water spray system was developed to compare and analyze the air-water arrangement options in IEC systems currently used in DCs, and the corresponding characteristics are explored from the perspective of CFD techniques to determine the effect of nozzle configurations on the formation and evaporation of water film within the wet channels. Then, parametric analysis of nozzle setup schemes based on performance metrics showed that the nozzle arranged in top-side configuration and paired with the air-water counterflow form had the best performance, with 59.2% and 27.4% improvement in water film coverage area and temperature drop, respectively, over the worst scheme (bottom configuration) at a water supply flow rate of 65 L/s. Finally, the effectiveness of the enhanced approach was simulated and analyzed for hydrophilic and fiber coatings, and it was found that the water film coverage increased by 14.5% and 31.6%, respectively, while the coefficient of performance (COP) increased by 7.4% and 16.1%.
Keywords: Data center
Energy recovery
Improvement
Indirect evaporative cooler
Nozzle configurations
Publisher: Elsevier
Journal: Journal of building engineering 
EISSN: 2352-7102
DOI: 10.1016/j.jobe.2023.107195
Rights: © 2023 Elsevier Ltd. All rights reserved.
© 2023. This manuscript version is made available under the CC-BY-NC-ND 4.0 license https://creativecommons.org/licenses/by-nc-nd/4.0/
The following publication Ma, X., Shi, W., & Yang, H. (2023). Improving the performance of indirect evaporative cooler for energy recovery from the perspective of nozzle configuration: A CFD model analysis. Journal of Building Engineering, 76, 107195 is available at https://doi.org/10.1016/j.jobe.2023.107195.
Appears in Collections:Journal/Magazine Article

Files in This Item:
File Description SizeFormat 
Ma_Improving_Performance_Indirect.pdfPre-Published version2.39 MBAdobe PDFView/Open
Open Access Information
Status open access
File Version Final Accepted Manuscript
Access
View full-text via PolyU eLinks SFX Query
Show full item record

Page views

70
Citations as of Nov 10, 2025

SCOPUSTM   
Citations

15
Citations as of Dec 5, 2025

WEB OF SCIENCETM
Citations

13
Citations as of Dec 4, 2025

Google ScholarTM

Check

Altmetric


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.