| Title: | Indirect evaporative cooler considering condensation from primary air : model development and parameter analysis | Authors: | Chen, Y Yang, H Luo, Y |
Issue Date: | Jan-2016 | Source: | Building and environment, Jan. 2016, v. 95, p. 330-345 | Abstract: | The indirect evaporative cooler (IEC), regarded as a low-carbon cooling device, was proposed as fresh air pre-cooling and heat recovery device in the air-conditioning system to break the region limitation of application in hot and humid areas. In this hybrid system, the exhausted air with low temperature and humidity from air-conditioned space is used as secondary air to cool the inlet fresh air. As the dew point temperature of the fresh air is high, condensation may occur in the dry channels. However, the modeling of IEC with condensation has been seldom studied and corresponding parameter study is also lacking. So the paper established a new numerical model taking the condensation from primary air into consideration. The model was validated by the published data from literature with good agreement. Nine parameters were analyzed in detail under three operation states (non-condensation, partial condensation and total condensation) using four evaluation indexes: condensation ratio, wet-bulb efficiency, enlargement coefficient and total heat transfer rate. The results show that the condensation lowers the wet-bulb efficiency of IEC but improves the total heat transfer rate due to dehumidification. | Keywords: | Condensation Indirect evaporative cooler Numerical modeling Parameter study |
Publisher: | Pergamon Press | Journal: | Building and environment | ISSN: | 0360-1323 | EISSN: | 1873-684X | DOI: | 10.1016/j.buildenv.2015.09.030 | Rights: | © 2015 Elsevier Ltd. All rights reserved. © 2015. This manuscript version is made available under the CC-BY-NC-ND 4.0 license https://creativecommons.org/licenses/by-nc-nd/4.0/. The following publication Chen, Y., Yang, H., & Luo, Y. (2016). Indirect evaporative cooler considering condensation from primary air: Model development and parameter analysis. Building and Environment, 95, 330-345 is available at https://doi.org/10.1016/j.buildenv.2015.09.030. |
| Appears in Collections: | Journal/Magazine Article |
Files in This Item:
| File | Description | Size | Format | |
|---|---|---|---|---|
| Yang_Indirect_Evaporative_Cooler.pdf | Pre-Published version | 1.22 MB | Adobe PDF | View/Open |
Page views
93
Last Week
3
3
Last month
Citations as of Nov 9, 2025
Downloads
137
Citations as of Nov 9, 2025
SCOPUSTM
Citations
89
Citations as of Dec 19, 2025
WEB OF SCIENCETM
Citations
87
Citations as of Dec 18, 2025
Google ScholarTM
Check
Altmetric
Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.