Please use this identifier to cite or link to this item:
http://hdl.handle.net/10397/102989
| Title: | CFD simulation of the effect of an upstream building on the inter-unit dispersion in a multi-story building in two wind directions | Authors: | Cui, DJ Mak, CM Kwok, KCS Ai, ZT |
Issue Date: | Mar-2016 | Source: | Journal of wind engineering and industrial aerodynamics, Mar. 2016, v. 150, p. 31-41 | Abstract: | Previous studies on inter-unit dispersion are limited to isolated buildings. The influence of an upstream interfering building may significantly modify the indoor airflow characteristics of the wind-induced natural ventilated downstream interfered building. Motivated by the findings in previous studies, namely that infectious respiratory aerosols exhausted from a unit can re-enter into another unit in the same building through building envelope openings, this study investigates the inter-unit pollutant dispersion around a multi-story building in two wind directions by employing the computational fluid dynamics (CFD) method. The CFD model employed in this study has been validated against previous experimental data. The results show that the presence of an upstream building greatly changes the path lines around the downstream target building and the pollutant transportation routes around it. The presence of a low upstream building also greatly increases the average air exchange rate (ACH) values and the pollutant re-entry ratios (Rk) below the source unit on the windward side of the downstream target building for normal wind incidence. However, the presence of a high upstream building greatly increases the average ACH values on the windward side and increases the Rk on the leeward side of the downstream building for oblique wind incidence. | Keywords: | CFD Inter-unit dispersion Natural ventilation Upstream building Wind directions |
Publisher: | Elsevier | Journal: | Journal of wind engineering and industrial aerodynamics | ISSN: | 0167-6105 | EISSN: | 1872-8197 | DOI: | 10.1016/j.jweia.2016.01.007 | Rights: | © 2016 Elsevier Ltd. All rights reserved. © 2016. This manuscript version is made available under the CC-BY-NC-ND 4.0 license https://creativecommons.org/licenses/by-nc-nd/4.0/. The following publication Cui, D. J., Mak, C. M., Kwok, K. C. S., & Ai, Z. T. (2016). CFD simulation of the effect of an upstream building on the inter-unit dispersion in a multi-story building in two wind directions. Journal of Wind Engineering and Industrial Aerodynamics, 150, 31-41 is available at https://doi.org/10.1016/j.jweia.2016.01.007. |
| Appears in Collections: | Journal/Magazine Article |
Files in This Item:
| File | Description | Size | Format | |
|---|---|---|---|---|
| Mak_CFD_Simulation_Effect.pdf | Pre-Published version | 4.79 MB | Adobe PDF | View/Open |
Page views
119
Last Week
6
6
Last month
Citations as of Nov 9, 2025
Downloads
84
Citations as of Nov 9, 2025
SCOPUSTM
Citations
48
Citations as of Dec 19, 2025
WEB OF SCIENCETM
Citations
43
Citations as of Dec 18, 2025
Google ScholarTM
Check
Altmetric
Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.