| Title: | Quantitative evaluation of the impact of building load characteristics on energy performance of district cooling systems | Authors: | Yan, C Gang, W Niu, X Peng, X Wang, S |
Issue Date: | 1-Nov-2017 | Source: | Applied energy, 1 Nov. 2017, v. 205, p. 635-643 | Abstract: | With the rapid increase of research and application of district cooling systems (DCS), the controversy whether DCS is really energy-efficient is intensifying. Building load characteristics of DCS may be a main reason for this controversy. However, how building load characteristics affect the energy performance and which load characteristics can ensure a high performance? To answer such critical questions and improve the energy performance of DCS, this paper presents a systematic method for quantitative analysis and evaluation of the impact of building load characteristics on the energy performance of DCS. Key energy performance indicators are proposed. The load characteristics of DCS are described and quantified by introducing the concept of Lorenz curve and Gini coefficient. “Grouping coefficient” is proposed to evaluate the rationality of grouping different buildings into the same branch of chilled water distribution system. Case studies are conducted to investigate the performance of DCS under different load characteristics and to compare with conventional cooling systems. The impact of Gini coefficient and grouping coefficient on the energy performance of chiller plant, chilled water distribution system and the whole DCS are analysed. Recommendations are provided for future's application of DCS and individual cooling systems. | Keywords: | Chilled water system District cooling system Energy efficiency Gini coefficient Load characteristic |
Publisher: | Pergamon Press | Journal: | Applied energy | ISSN: | 0306-2619 | EISSN: | 1872-9118 | DOI: | 10.1016/j.apenergy.2017.08.022 | Rights: | © 2017 Elsevier Ltd. All rights reserved. © 2017. This manuscript version is made available under the CC-BY-NC-ND 4.0 license https://creativecommons.org/licenses/by-nc-nd/4.0/. The following publication Yan, C., Gang, W., Niu, X., Peng, X., & Wang, S. (2017). Quantitative evaluation of the impact of building load characteristics on energy performance of district cooling systems. Applied Energy, 205, 635-643 is available at https://doi.org/10.1016/j.apenergy.2017.08.022. |
| Appears in Collections: | Journal/Magazine Article |
Files in This Item:
| File | Description | Size | Format | |
|---|---|---|---|---|
| Wang_Quantitative_Evaluation_Impact.pdf | Pre-Published version | 1.16 MB | Adobe PDF | View/Open |
Page views
100
Last Week
4
4
Last month
Citations as of Nov 9, 2025
Downloads
156
Citations as of Nov 9, 2025
SCOPUSTM
Citations
24
Citations as of Dec 19, 2025
WEB OF SCIENCETM
Citations
21
Citations as of Dec 18, 2025
Google ScholarTM
Check
Altmetric
Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.