Please use this identifier to cite or link to this item: http://hdl.handle.net/10397/102899
PIRA download icon_1.1View/Download Full Text
Title: Numerical study on indirect evaporative coolers considering condensation : a thorough comparison between cross flow and counter flow
Authors: Min, Y 
Chen, Y
Yang, H 
Issue Date: Mar-2019
Source: International journal of heat and mass transfer, Mar. 2019, v. 131, p. 472-486
Abstract: Indirect evaporative cooling is recognized as an alternative air-cooling solution with low carbon potential and considerable energy efficiency. An indirect evaporative cooler (IEC) can handle both of the sensible and latent cooling loads because of possible condensation when it is used as a precooling unit in an air-conditioning system in hot and humid regions. Cross flow and counter flow, as two basic flow configurations of an IEC, differ in condensation behavior that affects their cooling performance. In this paper, a novel 2-D model of cross flow IEC considering condensation is established and validated. The performance of the cross flow and counter flow IEC is thoroughly compared under the same configuration. The channel gap and height to length ratio (H/L) are optimized to provide references for the design and operation of the IEC under condensation conditions. Results show that under the same operating conditions, the condensation ratio of counter flow IEC is 2–15% higher than that of the cross flow IEC, leading to 2–7% decrease of wet-bulb effectiveness. The difference in the total heat transfer rate between the two configurations is less than 5% when the number of transfer units (NTUp) is lower than 3.1. For cross flow IEC, there is an optimal value in H/L among 0.4–0.8 considering the cooling capacity and energy consumption.
Keywords: Condensation
Counter flow
Cross flow
Indirect evaporative cooler
Numerical simulation
Optimization
Publisher: Pergamon Press
Journal: International journal of heat and mass transfer 
ISSN: 0017-9310
EISSN: 1879-2189
DOI: 10.1016/j.ijheatmasstransfer.2018.11.082
Rights: © 2018 Elsevier Ltd. All rights reserved.
© 2018. This manuscript version is made available under the CC-BY-NC-ND 4.0 license https://creativecommons.org/licenses/by-nc-nd/4.0/.
The following publication Min, Y., Chen, Y., & Yang, H. (2019). Numerical study on indirect evaporative coolers considering condensation: A thorough comparison between cross flow and counter flow. International Journal of Heat and Mass Transfer, 131, 472-486 is available at https://doi.org/10.1016/j.ijheatmasstransfer.2018.11.082.
Appears in Collections:Journal/Magazine Article

Files in This Item:
File Description SizeFormat 
Min_Numerical_Study_Indirect.pdfPre-Published version1.61 MBAdobe PDFView/Open
Open Access Information
Status open access
File Version Final Accepted Manuscript
Access
View full-text via PolyU eLinks SFX Query
Show full item record

Page views

93
Last Week
4
Last month
Citations as of Nov 9, 2025

Downloads

142
Citations as of Nov 9, 2025

SCOPUSTM   
Citations

88
Citations as of Dec 19, 2025

WEB OF SCIENCETM
Citations

81
Citations as of Dec 18, 2025

Google ScholarTM

Check

Altmetric


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.