Title: A risk-based robust optimal chiller sequencing control strategy for energy-efficient operation considering measurement uncertainties
Authors: Zhuang, C 
Wang, S 
Shan, K 
Issue Date: 15-Dec-2020
Source: Applied energy, 15 Dec. 2020, v. 280, 115983
Abstract: Proper and reliable control of central chilling systems with multiple chillers is crucial to save energy and enhance energy efficiency. The conventional total-cooling-load-based chiller sequencing control strategies determine switching (on/off) thresholds according to building instantaneous cooling load and chiller maximum cooling capacity. However, due to the existence of measurement uncertainties and ever-changing operating conditions, optimal switching points often deviate significantly from predefined thresholds. To deal with these challenges and uncertainties, a risk-based robust optimal chiller sequencing control strategy is proposed to improve the robustness and energy efficiency of chillers in operation. As the core of the control strategy, an online stochastic decision-making scheme, which is developed to optimize chiller staging based on quantified risks. The risk of failure to achieve expected operation performance by switching on/off a chiller is evaluated through analyzing the probabilistic fused cooling load and the probabilistic chiller maximum cooling capacity, based on Bayesian calibration of cooling load and capacity models. The best switching points can therefore be identified in a stochastic approach. The results of case studies show that the proposed strategy can improve the reliability and robustness of chiller sequence operation. Compared with the conventional strategy, the switching frequency was decreased by more than 54%, and the energy use of central cooling systems can be reduced by 2.8% without sacrificing thermal comfort.
Keywords: Bayesian calibration
Chiller sequencing
Measurement uncertainty
Risk-based control
Robust optimal control
Publisher: Pergamon Press
Journal: Applied energy 
ISSN: 0306-2619
EISSN: 1872-9118
DOI: 10.1016/j.apenergy.2020.115983
Rights: © 2020 Elsevier Ltd. All rights reserved.
© 2020. This manuscript version is made available under the CC-BY-NC-ND 4.0 license https://creativecommons.org/licenses/by-nc-nd/4.0/.
The following publication Zhuang, C., Wang, S., & Shan, K. (2020). A risk-based robust optimal chiller sequencing control strategy for energy-efficient operation considering measurement uncertainties. Applied Energy, 280, 115983 is available at https://doi.org/10.1016/j.apenergy.2020.115983.
Appears in Collections:Journal/Magazine Article

Files in This Item:
File Description SizeFormat 
Zhuang_Risk-Based_Robust_Optimal.pdfPre-Published version2.3 MBAdobe PDFView/Open
Open Access Information
Status open access
File Version Final Accepted Manuscript
Access
View full-text via PolyU eLinks SFX Query
Show full item record

Page views

126
Last Week
6
Last month
Citations as of Nov 9, 2025

Downloads

128
Citations as of Nov 9, 2025

SCOPUSTM   
Citations

35
Citations as of Dec 19, 2025

WEB OF SCIENCETM
Citations

33
Citations as of Dec 18, 2025

Google ScholarTM

Check

Altmetric


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.