Please use this identifier to cite or link to this item: http://hdl.handle.net/10397/101390
PIRA download icon_1.1View/Download Full Text
Title: Multiple discharges before leader inception in long air gaps under positive switching impulses
Authors: Zhao, X 
Lee, J
Liu, G
Jia, L
Liu, Y
He, J
Du, Y 
Issue Date: Feb-2023
Source: High voltage, Feb. 2023, v. 8, no. 1, p. 111-118
Abstract: There are multiple corona bursts before leader inception when the rising rate of the applied voltage or electric field is not sufficiently high enough in long positive sparks. In existing studies, no attention has been paid to whether these corona bursts occur in the same location, and they are mostly considered directly as belonging to the same discharge. However, this paper presents that in a typical rod-plate long air gap, the multiple corona bursts before leader inception are distributed in at least two different locations, and the highest probability of three discharges occurs. Also, the discharge occurs with the highest probability in the time sequence ‘tip-tip-side-tip-other side’ of the electrode in the first five corona bursts. For each discharge, the first corona current is a single, double exponential pulse, while the following corona currents are mostly a superposition of multiple pulses. The above findings are mainly based on experiments in a 1.4 m air gap under positive switching impulses, in which the voltage, current, and high-speed images were recorded simultaneously. Finally, based on the experimental results, this paper discusses the effects brought by ignoring the multiple discharges on key parameters of leader inception and makes some suggestions to optimise long spark experiments.
Publisher: The Institution of Engineering and Technology
Journal: High voltage 
EISSN: 2397-7264
DOI: 10.1049/hve2.12255
Rights: This is an open access article under the terms of the Creative Commons Attribution‐NonCommercial‐NoDerivs License (https://creativecommons.org/licenses/by-nc-nd/4.0/legalcode), which permits use and distribution in any medium, provided the original work is properly cited, the use is non‐commercial and no modifications or adaptations are made.
© 2022 The Authors. High Voltage published by John Wiley & Sons Ltd on behalf of The Institution of Engineering and Technology and China Electric Power Research Institute.
The following publication Zhao, X., Lee, J., Liu, G., Jia, L., Liu, Y., He, J., & Du, Y. (2023). Multiple discharges before leader inception in long air gaps under positive switching impulses. High Voltage, 8(1), 111-118 is available at https://doi.org/10.1049/hve2.12255.
Appears in Collections:Journal/Magazine Article

Files in This Item:
File Description SizeFormat 
High Voltage - 2022 - Zhao.pdf2.41 MBAdobe PDFView/Open
Open Access Information
Status open access
File Version Version of Record
Access
View full-text via PolyU eLinks SFX Query
Show full item record

Page views

113
Last Week
0
Last month
Citations as of Nov 9, 2025

Downloads

52
Citations as of Nov 9, 2025

SCOPUSTM   
Citations

3
Citations as of Dec 19, 2025

WEB OF SCIENCETM
Citations

3
Citations as of Dec 18, 2025

Google ScholarTM

Check

Altmetric


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.