Title: Simulation of carbon monoxide level in enclosed car parks using an air flow network program
Authors: Chow, WK 
Issue Date: 1996
Source: Tunnelling and underground space technology, 1996, v. 11, no. 2, p. 237-240 How to cite?
Journal: Tunnelling and Underground Space Technology 
Abstract: The indoor carbon monoxide concentration in 10 car parks with volumes varying from 1,000 m3 to 35,000 m3 and ceiling height of 3 m was simulated using the multi-zone network model CONTAM93/94 developed at the Building and Fire Research Laboratory of the National Institute of Standards and Testing (NIST) in the U.S.A. Use of the model in designing the ventilation system in a car park is illustrated. Experimental measurements on the carbon monoxide level in that car park were performed to verify the results.