Please use this identifier to cite or link to this item: http://hdl.handle.net/10397/80900
PIRA download icon_1.1View/Download Full Text
Title: Analysis of parallel operation characteristics of chillers under partial load conditions
Authors: Zheng, Y
Liu, X
Lu, Z
Fang, G 
Chen, W 
Deng, S 
Issue Date: 2019
Source: Energy procedia, 2019, v. 158, p. 3676-3681
Abstract: The rational allocation of chiller group plays an important role in the efficient operation of generating units. In this paper, the running characteristics of chiller group under full load are studied. Through the construction of the operation model of the chiller group, the relationship between the start and stop collocation and the operation characteristics of the unit group was explored, and the influence of the unit capacity configuration and the number of table number configuration on the running energy consumption characteristics was studied. The results showed that: the greater the difference of host capacity in the group, the lower the energy consumption under full load. In this example, the difference of energy consumption can reach 8%. At the same time, through the increase in the number of generating units, the difference in host capacity within the group had less impact on energy consumption at full load. For a unit group with the same host capacity, the more the number of units was configured, the lower the operating energy consumption. It provided theoretical support for the selection, collocation and operation management of chillers in practical projects.
Keywords: Characteristic analysis
Chiller group
Energy saving
Publisher: Elsevier
Journal: Energy procedia 
EISSN: 1876-6102
DOI: 10.1016/j.egypro.2019.01.892
Description: 10th International Conference on Applied Energy, ICAE 2018, Hong Kong, 22-25 August 2018
Rights: © 2019 The Authors. Published by Elsevier Ltd. This is an open access article under the CC BY-NC-ND license (http://creativecommons.org/licenses/by-nc-nd/4.0/) Peer-review under responsibility of the scientific committee of ICAE2018 – The 10th International Conference on Applied Energy.
The following publication Liu, X., Lu, Z., Fang, G., Chen, W., & Deng, S. (2019). Analysis of parallel operation characteristics of chillers under partial load conditions. Energy Procedia, 158, 3676-3681 is available at https://doi.org/10.1016/j.egypro.2019.01.892
Appears in Collections:Conference Paper

Files in This Item:
File Description SizeFormat 
Zheng_Analysis_parallel_operation.pdf545.86 kBAdobe PDFView/Open
Open Access Information
Status open access
File Version Version of Record
Access
View full-text via PolyU eLinks SFX Query
Show full item record

Page views

101
Last Week
2
Last month
Citations as of Apr 21, 2024

Downloads

170
Citations as of Apr 21, 2024

SCOPUSTM   
Citations

3
Citations as of Apr 26, 2024

WEB OF SCIENCETM
Citations

2
Citations as of Apr 25, 2024

Google ScholarTM

Check

Altmetric


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.