Please use this identifier to cite or link to this item: http://hdl.handle.net/10397/77459
PIRA download icon_1.1View/Download Full Text
Title: Probabilistic and electricity saving analyses of Mist Coolers for Chiller System in a Hotel
Authors: Yu, FW 
Ho, WT 
Chan, KT 
Sit, RKY 
Issue Date: 2017
Source: Energy procedia, 2017, v. 143, no. , p. 154-160
Abstract: This study investigates the optimization and electricity savings of an air-cooled chiller system with mist coolers. An air-cooled screw chiller having a nominal capacity of 282 kW was retrofitted with a mist cooler and dual condenser fan controls: fixed head pressure with constant speed and floating condensing temperature with variable speed. Comprehensive operating data logged at 5-min intervals were used to develop chiller models by random forest. The models served as a fitness function for genetic algorithm to predict the maximum coefficient of performance (COP) with optimal controlled variables under various operating conditions. Scatter plots of the optimal variables against the actual variables showed that to achieve the maximum COP, the set point of condensing temperature should be adjusted based on its measured value and the variation of heat rejection airflow rate. The probability of applying mist cooling was identified to be 70.91 - 78.33% for the simulated cooling load distribution of a hotel in a subtropical climate. Mist coolers with the optimal control brought electricity savings of 2.28 - 8.16%, depending on system configurations and condenser fan control modes. Fewer chillers in a system would result in more electricity savings from the optimal control while mist coolers complement the frequent full load operation of chillers to enhance electricity savings.
Keywords: Air-cooled chiller
Coefficient of performance
Genetic algorithm
Mist cooler
Random forest
Publisher: Elsevier
Journal: Energy procedia 
EISSN: 1876-6102
DOI: 10.1016/j.egypro.2017.12.664
Description: 1st Joint Conference on World Engineers Summit - Applied Energy Symposium and Forum: Low Carbon Cities and Urban Energy, WES-CUE 2017, Singapore, 19-21 2017
Rights: © 2017 The Authors.
The following publication Yu, F. W., Ho, W. T., Chan, K. T., & Sit, R. K. Y. (2017). Probabilistic and electricity saving analyses of Mist Coolers for Chiller System in a Hotel. Energy Procedia, 143, 154-160 is available athttps://dx.doi.org/10.1016/j.egypro.2017.12.664
Appears in Collections:Conference Paper

Files in This Item:
File Description SizeFormat 
Yu_Probabilistic_Electricity_Saving.pdf821.68 kBAdobe PDFView/Open
Open Access Information
Status open access
File Version Version of Record
Access
View full-text via PolyU eLinks SFX Query
Show full item record

Page views

123
Last Week
1
Last month
Citations as of Apr 14, 2024

Downloads

59
Citations as of Apr 14, 2024

SCOPUSTM   
Citations

3
Citations as of Apr 19, 2024

WEB OF SCIENCETM
Citations

2
Last Week
0
Last month
Citations as of Apr 18, 2024

Google ScholarTM

Check

Altmetric


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.