Please use this identifier to cite or link to this item: http://hdl.handle.net/10397/76012
Title: Supply-based feedback control strategy of air-conditioning systems for direct load control of buildings responding to urgent requests of smart grids
Authors: Wang, SW 
Tang, R 
Keywords: Fast demand response
Smart grid
Supply-based feedback control
Adaptive utility function
Direct load control
Building demand management
Issue Date: 2017
Publisher: Pergamon Press
Source: Applied energy, 2017, v. 201, p. 419-432 How to cite?
Journal: Applied energy 
Abstract: Power demand response (DR) of buildings is considered as one of most promising solutions to power imbalance and reliability issues in smart grids while demand response control of air-conditioning systems is a most effective means. A fast demand response control strategy, direct load control by shutting down part of operating chillers, has received great attention in recent DR researches and applications. This method, however, would lead to uneven indoor air temperature rises among individual airconditioned spaces due to the failure of proper distribution of limited cooling supply by the conventional demand-based feedback control strategy commonly used today. A novel supply-based feedback control strategy is therefore proposed to effectively solve the problems caused by the fast demand response and power limiting control strategy. This proposed strategy employs global and local cooling distributors based on adaptive utility function to reset the set-points of chilled water flow and air flow for each zone and space online. Simplified offline and online identification methods, for the two parameters respectively, ensure the convenience and robustness of the adaptive utility function in applications. Case studies are conducted on a simulated air-conditioning system to test and validate the proposed control strategy. Results show that the proposed control strategy is capable not only to maintain even indoor air temperature rises, but also to avoid the operation problems during DR events. Moreover, rather high indoor relative humidity is obviously decreased. The power rebound phenomenon is also relieved and the original comfort control of spaces can be resumed much quickly.
URI: http://hdl.handle.net/10397/76012
ISSN: 0306-2619
EISSN: 1872-9118
DOI: 10.1016/j.apenergy.2016.10.067
Appears in Collections:Journal/Magazine Article

Access
View full-text via PolyU eLinks SFX Query
Show full item record

SCOPUSTM   
Citations

12
Last Week
0
Last month
Citations as of Dec 13, 2018

WEB OF SCIENCETM
Citations

7
Last Week
0
Last month
Citations as of Dec 13, 2018

Page view(s)

13
Citations as of Dec 9, 2018

Google ScholarTM

Check

Altmetric


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.