Abstract: To enhance the performance of doubly fed induction generator (DFIG) wind turbine during low voltage events, a battery energy storage system (BESS) together with advanced control schemes are proposed. The novel control strategy utilizes the existing devices within the DFIG wind turbine system to achieve low voltage ride through (LVRT) by controlling rotor and grid side converters and BESS. The advanced control scheme can save the major excessive power into turbine inertia by accelerating the turbine rotating speed. Therefore, relatively small quantity of power will flow into dc-link, which can reduce the capacity of BESS. Moreover, the sequence of control scheme and BESS activation time was discussed in this paper which can help us to determine the battery charging period. Through this cooperated control scheme, the sensitive power electronics devices can be protected against current and voltage fluctuations. The proposed control scheme is validated through dynamic simulations.
Description: 10th International Conference on Advances in Power System Control, Operation and Management, APSCOM 2015, Hong Kong, 8-12 November 2015
URI: http://hdl.handle.net/10397/66186
Appears in Collections:Conference Paper

Access
View full-text via PolyU eLinks SFX Query
Show full item record

Page view(s)

13
Checked on Aug 21, 2017

Google ScholarTM

Check



Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.