Title: Proposal of using a time constant for specifying atrium smoke filling in fire codes
Authors: Chow, WK 
Li, J
Issue Date: 2000
Publisher: Hong Kong Polytechnic University, Dept. of Building Services Engineering
Source: International journal on engineering performance-based fire codes, 2000, v. 2, no. 2, p. 58-60 How to cite?
Journal: International journal on engineering performance-based fire codes 
Abstract: A time constant including building geometry and design fire characteristics was suggested for specifying smoke filling in atria. From the survey results on 138 local atria, time constants of 73 atria were calculated. The smoke filling times required to fill 80 % of the space volume were evaluated from the NFPA smoke filling equation with a slow t2-fire. The time for the smoke front to reach the ceiling was taken into account. It is further confirmed that time constant is a better parameter than the space volume used in the current fire codes, and is thus recommended to the Authority.
URI: http://hdl.handle.net/10397/62806
ISSN: 1561-9559
Appears in Collections:Journal/Magazine Article

Access
View full-text via PolyU eLinks SFX Query
Show full item record

Page view(s)

23
Last Week
2
Last month
Checked on Sep 24, 2017

Google ScholarTM

Check