Title: Experimental study of personalized air system for the reduction of pollutant exposure
Authors: Zuo, Huigang
Keywords: Hong Kong Polytechnic University -- Dissertations
Air conditioning
Displacement ventilation
Air quality
Indoor air pollution
Issue Date: 2004
Publisher: The Hong Kong Polytechnic University
Abstract: Current ASHRAE ventilation standard promulgates an outdoor intake around 10 1/s per person, with certain variations depending on building types. On the other hand, the metabolic human respiration rate for air is only around 0.11/s. In this thesis, we tested the concept of supplying ventilation in close proximity to nostrils and the facial area at much reduced airflow rate. A thermal manikin with a simulated lung is placed in a normal air-conditioned office. Fresh air supply is directed at the facial area of the manikin at flow rates raging from 0.1 to 41/s. The performance of personalized ventilation based on air movement in the vicinity of the occupant depends to a large extent on the supply air terminal device. Eight different air terminal devices were developed, tested and compared. CO₂ was used as a tracer gas, and injected into the supply air, and the CO₂ concentrations in the inhaled air, supplied air, and the ambient room air were measured, which were used to calculate two newly defined indices, i.e., the fresh air utilization efficiency ηu and the pollutant exposure reduction effectiveness ηPER. In the air supply flow rate range tested, the pollutant exposure reduction effectiveness increased with the increase of the airflow rate from the ATD to a maximum value. Further increase of the airflow rate appears to have reduced impact on the pollutant exposure reduction effectiveness. The effects of the airflow around thermal manikin due to heat convection, the supply airflow rate, the cross-sectional area of air terminal devices and the geometry of air terminal devices were studied. Under both isothermal and non-isothermal conditions and an airflow rate below 4 L/s, a middle size circular air terminal device achieved the highest pollutant exposure reduction effectiveness 0.8. It is perceived that such a facial air supply method may have application potentials in those work places where occupants are sitting in a fixed position for prolonged period. An optimal air terminal device was recommended which has the best performance in improving an occupants' inhaled air quality.
Description: xii, 100 leaves : ill. ; 30 cm.
PolyU Library Call No.: [THS] LG51 .H577M BSE 2004 Zuo
URI: http://hdl.handle.net/10397/3735
Rights: All rights reserved.
Appears in Collections:Thesis

Files in This Item:
File Description SizeFormat 
b17565820_link.htmFor PolyU Users 162 BHTMLView/Open
b17565820_ir.pdfFor All Users (Non-printable) 3.34 MBAdobe PDFView/Open
Show full item record

Page view(s)

373
Last Week
2
Last month
Checked on Feb 26, 2017

Download(s)

228
Checked on Feb 26, 2017

Google ScholarTM

Check



Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.