Please use this identifier to cite or link to this item: http://hdl.handle.net/10397/33334
Title: Assessment on thermal sensitivity of fusable links with a wind tunnel
Authors: Chow, WK 
Cheng, ACK
Issue Date: 2007
Source: 2007 Proceedings of the ASME/JSME Thermal Engineering Summer Heat Transfer Conference - HT 2007, 2007, v. 3, p. 621-624 How to cite?
Journal: 2007 Proceedings of the ASME/JSME Thermal Engineering Summer Heat Transfer Conference - HT 2007 
Abstract: This is a paper on exploring how codes on assessing thermal sensitivity of fusable links for controlling fire shutters can be established. Typical samples of fusable links were tested in a wind tunnel for studying the thermal response of sprinkler heads. In the test, the fusable link samples were loaded under 0.4 kgf. The working section of the tunnel was set at air temperature of 135°C and air speed of 2.54 ms-1. Results suggested that it is feasible to assess the thermal sensitivity of fusable links by following international testing standards.
Description: 2007 ASME/JSME Thermal Engineering Summer Heat Transfer Conference, HT 2007, Vancouver, BC, 8-12 July 2007
URI: http://hdl.handle.net/10397/33334
ISBN: 0791842746
9780791842744
DOI: 10.1115/HT2007-32035