Title: Direct torque control of doubly fed induction generators connected to grids with unbalanced voltage
Authors: Wong, KC
Ho, SL 
Cheng, KWE 
Keywords: Doubly fed induction generators
Negative sequence
Unbalanced operation
Variable-speed generation
Issue Date: 2009
Publisher: Taylor & Francis
Source: Electric power components and systems, 2009, v. 37, no. 8, p. 894-913 How to cite?
Journal: Electric power components and systems 
Abstract: This article describes a direct control method for doubly fed induction generators that are connected to networks with unbalanced grid voltage. As the proposed method employs direct feedback of the torque and reactive power of the doubly fed induction generators in the control of power generation, it requires less computational power than methods using cascaded control loops. In the proposed algorithm, the feedback and control variables are separated into symmetrical components; they are independently controlled to i) realize the minimization of the undesirable stator power ripples or torque ripples arising from the unbalanced voltages in the three-phase supply and ii) regulate the torque and reactive power independently at variable speeds. The proposed method is validated by computer simulation and experimental results.
URI: http://hdl.handle.net/10397/32866
ISSN: 1532-5008
EISSN: 1532-5016
DOI: 10.1080/15325000902817275
Appears in Collections:Journal/Magazine Article

Access
View full-text via PolyU eLinks SFX Query
Show full item record

SCOPUSTM   
Citations

1
Last Week
0
Last month
0
Citations as of Aug 11, 2017

WEB OF SCIENCETM
Citations

1
Last Week
0
Last month
0
Citations as of Aug 14, 2017

Page view(s)

37
Last Week
2
Last month
Checked on Aug 13, 2017

Google ScholarTM

Check

Altmetric



Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.