Title: Emergency lighting monitoring system using LonWorks
Authors: Tse, WL
Chan, WL 
Lai, SS
Keywords: Battery-backup emergency lighting system
Distributive monitoring system
Intelligent control node
LonWorks
Maintenance test
Issue Date: 2003
Publisher: Elsevier
Source: Automation in construction, 2003, v. 12, no. 5 spec., p. 617-629 How to cite?
Journal: Automation in construction 
Abstract: As enforced by Fire Services Department in Hong Kong, indoor battery-backup emergency lighting is required to be tested monthly. A new distributive monitoring system is developed using LonWorks technology to cater for this. The system has several distinctive features - higher reliability, cost effectiveness and user friendliness. A low-cost electronic circuit board and a LonWorks control module are integrated with the existing emergency lighting circuit to form an intelligent control node in which the maintenance test is performed automatically. The test results are then sent to a control center via a LonWorks network. Any defective lighting point can be spotted without extensive effort on patrolling. Thus, higher reliability of the lighting system is achieved with significant reduction in maintenance cost.
URI: http://hdl.handle.net/10397/30121
ISSN: 0926-5805
EISSN: 1872-7891
DOI: 10.1016/S0926-5805(03)00055-4
Appears in Collections:Journal/Magazine Article

Access
View full-text via PolyU eLinks SFX Query
Show full item record

SCOPUSTM   
Citations

4
Last Week
0
Last month
0
Citations as of Aug 18, 2017

WEB OF SCIENCETM
Citations

3
Last Week
0
Last month
0
Citations as of Aug 21, 2017

Page view(s)

33
Last Week
4
Last month
Checked on Aug 21, 2017

Google ScholarTM

Check

Altmetric



Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.