Please use this identifier to cite or link to this item: http://hdl.handle.net/10397/2838
Title: Statistical modelling and forecasting schemes for air-conditioning system
Authors: Yiu, Chi-man Jacob
Keywords: Hong Kong Polytechnic University -- Dissertations
Air conditioning -- Energy consumption -- Mathematical models
Energy consumption -- Forecasting -- Mathematical models
Systems engineering -- Mathematical models
Issue Date: 2008
Publisher: The Hong Kong Polytechnic University
Abstract: System identification is a procedure to characterize the dynamic behaviour of a system, a sub-system or individual components based on measured data. This thesis presents a study on the modelling and parameter identification of air-conditioning processes by using the mathematical black-box modelling technique -AutoRegressive Moving Average eXogeneous (ARMAX) structure. A generic Multiple Input Multiple Output (MIMO) ARMAX structure has been developed for typical air-conditioning systems and the Recursive Least Square (RLS) method is used for model parameters identification. The performance of the model developed is compared with that of the Single Input Single Output (SISO) ARMAX model. Different combinations of ARMAX orders and forgetting factors are examined for the SISO and MIMO models in order to evaluate the optimum settings that maximize their accuracy. Measured data from an air-conditioning system in an existing building were used to test and validate the SISO and MIMO models. Using the MIMO ARMAX structure, a forecasting scheme for the air-conditioning system has been developed. The technique of conditional expectations at one step ahead is explained in the scheme development. The forecasting scheme is further applied to examine the system performance and predict the cooling load by a day-ahead forecast. The ARMAX model proves remarkably to examine the dynamic performance of an air-conditioning system. In addition, with the use of field data, the model shows great potential for system performance forecasting. An advanced control strategy for the air-conditioning system based on ARMAX model is also proposed.
Description: xix, 181 leaves : ill. (some col.) ; 30 cm.
PolyU Library Call No.: [THS] LG51 .H577P BSE 2008 Yiu
URI: http://hdl.handle.net/10397/2838
Rights: All rights reserved.
Appears in Collections:Thesis

Files in This Item:
File Description SizeFormat 
b21900425_link.htmFor PolyU Users162 BHTMLView/Open
b21900425_ir.pdfFor All Users (Non-printable) 1.99 MBAdobe PDFView/Open
Show full item record

Page view(s)

608
Last Week
3
Last month
Checked on Apr 23, 2017

Download(s)

736
Checked on Apr 23, 2017

Google ScholarTM

Check



Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.