Title: Stability of interacting grid-connected power converters
Authors: Wan, C
Huang, M
Tse, CK 
Ruan, X
Issue Date: 2014
Publisher: Institute of Electrical and Electronics Engineers Inc.
Source: Proceedings - IEEE International Symposium on Circuits and Systems, 2014, 6865722, p. 2668-2671 How to cite?
Abstract: The power grid in a typical micro distribution system is non-ideal, presenting itself as a voltage source with significant impedance. Thus, grid-connected converters interact with each other via the the non-ideal grid. In this study, we consider the practical scenario of voltage-source converters connected to a three-phase voltage source with significant impedance. We show that stability can be compromised in the interacting converters. Specifically, the stable operating regions in selected parameter space may be reduced when grid-connected converters interact under certain conditions. In this paper, we develop bifurcation boundaries in the parameter space with respect to Hopf-type instability. A small-signal model in the dq-frame is adopted to analyze the system using an impedance-based approach. Moreover, results are presented in design-oriented forms so as to facilitate the identification of variation trends of the parameter ranges that guarantee stable operation.
Description: 2014 IEEE International Symposium on Circuits and Systems, ISCAS 2014, Melbourne, VIC, 1-5 June 2014
URI: http://hdl.handle.net/10397/28297
ISBN: 9781479934324
ISSN: 0271-4310
DOI: 10.1109/ISCAS.2014.6865722
Appears in Collections:Conference Paper

Access
View full-text via PolyU eLinks SFX Query
Show full item record

Page view(s)

23
Last Week
0
Last month
Checked on Aug 20, 2017

Google ScholarTM

Check

Altmetric



Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.