Title: Performance of a novel HVAC system in hot and humid weather conditions : chilled-ceiling combined with desiccant cooling
Authors: Niu, JL 
Zuo, HG
Zhang, LZ
Keywords: Dehumidification
Energy saving
Humidity
Radiant cooling
Issue Date: 2002
Publisher: Hong Kong Institution of Engineers
Source: HKIE transactions, 2002, v. 9, no. 2, p. 25-29 How to cite?
Journal: HKIE transactions 
Abstract: A non-traditional HVAC (Heating, Ventilating, and Air-conditioning) system: chilled-ceiling combined with desiccant cooling, is proposed for hot and humid regions like Hong Kong. The performance of the combined system is investigated by a building energy simulation code named accuracy. The energy savings effect of the system in comparison with a conventional all-air system is investigated. The indoor humidity variations with the system are predicted by a room moisture balance method. It is found that to address the problem of water condensation on ceiling panels, a one-hour in advance air dehumidification is required for this novel system.
URI: http://hdl.handle.net/10397/27271
ISSN: 1023-697X
EISSN: 2326-3733
Appears in Collections:Journal/Magazine Article

Access
View full-text via PolyU eLinks SFX Query