Please use this identifier to cite or link to this item: http://hdl.handle.net/10397/25160
Title: Study on adaptive relay protection scheme based on phase measurement unit (PMU)
Authors: Fan, C
Li, S
Yu, W
Li, KK
Keywords: EMTP
Electric impedance
Phase measurement
Power transmission protection
Relay protection
Issue Date: 2004
Publisher: IET
Source: Eighth IEE International Conference on Developments in Power System Protection, 2004, 5-8 April 2004, v. 1, p. 36-39 How to cite?
Journal: Eighth IEE International Conference on Developments in Power System Protection, 2004, 5-8 April 2004 
Abstract: An adaptive setting scheme for distance protection relay based on phasor measurement unit (PMU) is proposed in this paper. Impedance of the transmission line is calculated to implement on-line setting of first zone distance protection. The voltages and currents of the two terminals of the transmission line and the current of the next transmission line from PMU can be used to obtain the synthetical system impedance that is used to obtain branch coefficient to implement online setting of second zone protection. Co-ordinated setting of distance protective relays can be carried out by the proposed method. Extensive EMTP simulation results have indicated that the equivalent operation mode of power system and the branching factor of protection can be obtained, and the on-line setting scheme can further raise the sensitivity of protection as well as insuring the selectivity and reliability of protection.
URI: http://hdl.handle.net/10397/25160
ISBN: 0-86341-385-4
ISSN: 0537-9989
DOI: 10.1049/cp:20040057
Appears in Collections:Conference Paper

Access
View full-text via PolyU eLinks SFX Query
Show full item record

Page view(s)

25
Last Week
1
Last month
Checked on Jun 18, 2017

Google ScholarTM

Check

Altmetric



Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.