Please use this identifier to cite or link to this item: http://hdl.handle.net/10397/24499
Title: Identifying faulty insulators by the method of discharge strength vector imbalance
Authors: Zhang, BD
Chan, WL 
Tsang, KM 
Huang, DP
Keywords: Discharging strength vector
Fault diagnosis
Faulty insulator
Local discharge
Issue Date: 2003
Publisher: 中国电机工程学会
Source: 中国电机工程学报 (Proceedings of the Chinese Society for Electrical Engineering), 2003, v. 23, no. 8, p. 130-134 How to cite?
Journal: 中国电机工程学报 (Proceedings of the Chinese Society for Electrical Engineering) 
Abstract: When there is any faulty insulator in high-voltage transmission, serious accidents may take place in power system at any moment. The pulse current method is used to detect discharge pulses from three-phase insulator strings, and the analytical method of discharge strength vector imbalance based on the three-phase imbalance method is put forward. This method depicts the distribution of discharge pulses using discharge strength vectors, and identifies faulty insulators with the help of the sum of discharge strength vectors and the imbalance of apparent discharge strengths in different regions. At the same time, the C-mean clustering method is used to eliminate abnormal statistical information and the increment method to solve the asymmetry of the discharge strength vectors of normal three-phase insulator strings. The experiment results of 110 kV three-phase insulator strings show that identifying faulty insulators by the method of discharge strength vector imbalance is effective.
URI: http://hdl.handle.net/10397/24499
ISSN: 0258-8013
Appears in Collections:Journal/Magazine Article

Access
View full-text via PolyU eLinks SFX Query
Show full item record

SCOPUSTM   
Citations

3
Citations as of Apr 30, 2016

Page view(s)

23
Last Week
2
Last month
Checked on Aug 13, 2017

Google ScholarTM

Check



Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.