Title: Tracking a ceiling jet front for hot smoke tests in tunnels
Authors: Hu, LH
Huo, R
Li, YZ
Yi, L
Deng, ZH
Wang, HB
Chow, WK 
Yuan, HY
Chen, T
Keywords: Ceiling jet front tracking
Infrared beam
Thermocouple
Issue Date: 2007
Publisher: SAGE Publications
Source: Journal of fire sciences, 2007, v. 25, no. 2, p. 99-108 How to cite?
Journal: Journal of fire sciences 
Abstract: There are difficulties in tracking the ceiling jet front while carrying out hot smoke tests in long tunnels with a small fire. In this study, an experimental method using infrared beams is suggested. The arrival time of the hot ceiling jet front to a designated position is measured by the abrupt attenuation of the infrared beam intensity. Field measurements are carried out in an underground tunnel of length 88 m. Diesel pool fires up to 1.5 MW are studied. The results on tracking the ceiling jet front are compared with the measurements by using the thermocouples, thermal resistors, and visual observations. This method is demonstrated to be useful for tracking the ceiling jet front at positions further away from the fire. Therefore, the method is suitable for studying the ceiling jet in hot smoke tests for evaluating smoke management systems in long tunnels.
URI: http://hdl.handle.net/10397/24456
ISSN: 0734-9041
EISSN: 1530-8049
DOI: 10.1177/0734904107065888
Appears in Collections:Journal/Magazine Article

Access
View full-text via PolyU eLinks SFX Query
Show full item record

SCOPUSTM   
Citations

5
Last Week
0
Last month
0
Citations as of Sep 11, 2017

WEB OF SCIENCETM
Citations

3
Last Week
0
Last month
0
Citations as of Sep 21, 2017

Page view(s)

50
Last Week
1
Last month
Checked on Sep 17, 2017

Google ScholarTM

Check

Altmetric



Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.