Please use this identifier to cite or link to this item: http://hdl.handle.net/10397/20465
Title: Simulation Study of Impact of Transformer Excitation Inrush Current on Oil-fired Thermal Plants as Black-Start Sources
Authors: Yu, T
Wei, MF
Ren, Z
Chan, KW 
Keywords: EMTP
Power generation faults
Power grids
Power transformers
Thermal power stations
Issue Date: 2005
Publisher: IEEE
Source: 2005 IEEE/PES Transmission and Distribution Conference and Exhibition: Asia and Pacific, 15-18 August 2005, Dalian, p. 1-4 (CD-ROM) How to cite?
Abstract: The oil-fired thermal plants, which are regarded as the important black-start sources in the Guangdong power grid, often fail in charging the idle-load transformers owing to the severe impacts of the excitation inrush currents. Because of the complexity of the load and the control systems, the quantitative analysis method is not suitable for this problem. In the paper, the explanation of the relevant mechanism is also provided, and the detailed model-based electromagnetic transient simulation is implemented to study the complex dynamic behaviors of oil-fired thermal plant in the preliminary stage of black-start. The simulation results show that the multi-machines and proper load connected with the generation will help reduce the impacts of transformer excitation inrush current on plants
URI: http://hdl.handle.net/10397/20465
ISBN: 0-7803-9114-4
DOI: 10.1109/TDC.2005.1546759
Appears in Collections:Conference Paper

Access
View full-text via PolyU eLinks SFX Query
Show full item record

Page view(s)

25
Last Week
0
Last month
Checked on Jun 18, 2017

Google ScholarTM

Check

Altmetric



Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.